HomeMy WebLinkAbout1995 01 11 - Lift Station ChecklistLIFT STATION MAINTENANCE
ITEMIZED CHECKLIST
AS PER R.B. VOTAPKA'S INSPECTION
ON JANUARY 11, 1995
1. No. 1 New belts are to be installed
2. No. 2 Loud hum in contactor for Pump No. 1; the Ammeter
registers the amperage for the pumps extremely low;
it should be replaced
Pump No. 1 is running at lower amps than Pump No. 2
Need to order an elapsed time meter to replace an
existing one
3. No. 3 Pump No. 2 had higher amperage than Pump No. 1 and
L3 had "0" amps
4. No. 4 Pump No. 1 is operating longer than Pump No. 2 -
Check alternating relay by manipulating the floats
5. No. 5 Roaches in bottom of panel - Seal holes in conduits
and spray inside with roach spray
6. No. 6 The "Lead Pump" light was on for some unexplained
reason while the pump was not running -- maybe due
to a short. Flasher unit was melted and making a
noise -- it has to be replaced [1 amp ST -0124
Flasher]
7. Sebastian Elementary School
No fuses in panel box
8. City Hall
"Power Burnout" light was on, yet the station
operated normally
9. Captain Hiram's
Need fuses in station; voltage is very high on L2
(298 volts); pump running lights don't work; one
relay chattered for awhile
10. Park Place
Pump 2 had higher amps than Pump 1 and L1 had "0"
amps.
General Note: Need to get the F.L.A. (Full Load Amps) for all
lift stations where it is not posted
RBV/jw