Date 5/10/ 2023
Fire Inspection Report
Inspector Contact: Sandy Seeley sseeley@cityofsebastian.org 874-3179
Occupancy Name Sebastian Saltwater Sea
Address 1732 Indian River Drive
Inspection Type Annual Fire
Occ. Type Assembly/Restaurant
Phone 918-4229
Contact Name Joe Laschiavo Email manager@sebastiansaltwater.com
NOTICE OF FIRE AND SAFETY HAZARDS: You are hereby notified that an inspection of your premises has disclosed the following fire hazards
and/or violation of standards of the National Fire Prevention Association (NFPA) adopted by The Florida Fire Prevention Code. As such conditions
are contraryto law, you are hereby required to correct Bald conditions upon receipt of this notice. A re -inspection to determine compliance will be
conducted on or after the scheduled re -inspection date ( 1. Failure to comply with the forgoing order before the date of such re -
I VIOLATIONS FIRE SYSTEMS PRESENT LlAlarm LISprinkler I°IHood LlStandpipe I...IFire Pump IJGenerator I
ADDRESS
01A Each bay/unit shall be identified by 6-in numbers for letters, contrasting color, visible from the roadway, at front and rear exits.
❑° 1B Knox entry system required; Type/location rewrnmend w .knoxbox.wm 3200 series wmmercial Yes: BOX: _ Switch
❑SC Truss signage required; Type/location: Yes: Type/Location:
ELECTRICAL
&A Extension cords use is not allowed in lieu of permanent wiring. Location(s): bar to overhead lights
❑2B Remove all storage within 3 feet of electrical panels. Location(s):
02C The use of non -listed multi -plug adapters are not allowed. Only UL listed type (surge type).
❑21) Breakers in the electrical panels must be legibly marked indicating their purpose and/or area of service.
❑2E All wiring shall be protected in approved conduit.
❑2F Open wire splices are required to be in a junction or receptacle box with a cover plate.
❑2G Electrical panel must have voids filled with approved spacers.
❑2H Wiring is damaged. Replace or properly repair. Location(s):
EXITS
❑3A Install or repair exit and/or emergency lighting. Location(s):
❑3B Door is not functioning properly. Location(s):
❑3C Exits shall be free of furnishing, decoration, or other objects that obstruct exit access and/or visibility thereof.
❑3D Fire exit hardware shall not have additional locks, latches or devices that inhibit its function or are not listed/approved.
❑3E Secondary exit door has an improper lock. Deadbolts shall not require the use of a key from the inside of the building.
❑3F Enclosed stairs shall be prohibited for use of any type of storage. No storage is allowed under or within 10 ft of exterior stairs.
FIRE EXTINGUISHERS
❑° 4A Provide service or inspection by a state licensed company for all fire extinguisher annually.
114B Extinguishers are required to be properly mounted along an exit access with the top no higher than 5 feet.
❑4C Fire extinguisher(s) required. Provide _ extinguisher(s) of a 2A10BC minimum rating per NFPA 10.
GENERAL AND STORAGE
❑5A Compressed gas cylinders/tanks shall be stored, appropriately secured, and identified with the product name.
❑5B Fire Systems need corrections: Hood and cleaning not in Compliance Engine
NOTES: 4A fire ext upstairs was missed on the last fire ext insp. Handrail going to 2nd story must dead end to the wall.
Gas shut off sign needed on the Natural gas. See attachement.
Recipient: Compliant Date:
Inspector: Inspector:
CITY OF
HOME OF PELICAN M9 D
BWH G DEPARTMENT
FIRE PREVENTION 0MCE
Fire Inspection Report
IM MMN STREET• SEBASrNN. FLORIDA 329 Inspector Contact: Sandy Seeley 873-3179 Sseeley@cityofsebastian.org
TELEPHONE (7M) F09-3031 FM (TM 5B9-=
Date 05 / 10 /23 Occupancy Name Sebastian Saltwater Seafood 1732 I.R. Drive, Sebastian
NOTICE OF FIRE AND SAFETY HAZARDS: You are hereby notified that an inspection of your premises has disclosed the following fire hazards
and/or violation of standards of the National Fire Prevention Association (NFPA) adopted by The Florida Fire Prevention Code. As such conditions
are contrary to law, you are hereby required to correct said conditions upon receipt of this notice. A re -inspection to determine compliance will be
conducted on or after the scheduled re -inspection date. Failure to comply with the forgoing order before the date of such re -inspection may render
you liable to the penalties provide by law for such violation.
NOTES: The underside of the stairs
rated drywall). NFPA 101 7-1.3.2.
to the 2nd floor must have a fire resistant rating of 1 hour minimum (2 layer of fire
The apartment unit on the second floor of the bar was installed with out a permit. If you want to continue the use of as
an apartment, a permit will be required. In that case, an automatic fire sprinkler system would be required to be installed.
Compliant Date:
Inspector: