HomeMy WebLinkAboutFIRE ANNUAL FOR 806 INDIAN RIVER DR. MULLIGANSclry of
SEB�TIAN Fire Inspection Report
HOME OF PELICAN ISLAND
DDILDING DEPARTMENT
FIRE PREVENTION OFFICE
12P MAINSTUEF-SEBASTUN.FLORIDA329 Inspector Contact: Sandy Seeley sseeley@cityofsebastian.org 874-3179
MEPHONt: (]P) S99 W7 FAx (>T2) 509-2.556
Date / / 3 Inspection Type Fire Inspection
Occupancy Name Mulligans Occ. Type Assembly/Restaurant
Address 806 Indian River Dr Sebastian, FL 32958 _ Phone 783-6727
S l R o ee L��!I:J-��-t �' * F .s�,�tv1C��mar Contact Name teve e Email �, o QY� O Q
NOTICE OF FIRE AND SAFETY HAZARDS: You are hereby notified that an inspection of your premises has disclosed the following fire hazards
and/or violation of standards of the National Fire Prevention Associ lion (NFPA) adopted by The Florida Fire Prevention Code. As such conditions
are contrary to law, you are hereby required to correct said nditi n on receipt of this notice. A re -inspection to determine compliance will be
conducted on or after the scheduled re -inspection date ( ).Failure to comply with the forgoing order before the date of such re-
insoection may render you liable to the oenalties orovide by law for such violation.
I VIOLATIONS FIRE SYSTEMS PRESENT LlAlarm LSprinkler LlHood UStandpipe LJFire Pump LJGenerator I
Each bay/unit shall be identified by 6-in numbers for letters,
Knox entry system required; Type/location )(G C—b
Truss signage required; Type/location:
20
stjng color, visible from the iroadway, at front and rear�tity, O�
Yes: Box: _ Switch _ eC/iv-
Yes: Type/Location:
ELECTRICAL
❑2A Extension cords use is not allowed in lieu of permanent wiring. Location(s):
❑2B Remove all storage within 3 feet of electrical panels. Location(s):
❑2C The use of non -listed multi -plug adapters are not allowed. Only UL listed type (surge type).
112D Breakers in the electrical panels must be legibly marked indicating their purpose and/or area of service.
❑2E All wiring shall be protected in approved conduit.
❑2P Open wire splices are required to be in a junction or receptacle box with a cover plate.
❑2G Electrical panel must have voids filled with approved spacers
T,�t j^ a�
Pill Wiring is damaged. Replace or properly repair. Location(s): \�� OLLI e_ CV,yl i
S
3A Install or epair i and r emergency lighting. Location(s):
03B Door is not functioning properly. Location(s):
❑3C Exits shall be free of furnishing, decoration, or other objects that obstruct exit access and/or visibility thereof.
❑3D Fire exit hardware shall not have additional locks, latches or devices that inhibit its function or are not listed/approved.
❑3E Secondary exit door has an improper lock. Deadbolts shall not require the use of a key from the inside of the building.
❑3F Enclosed stairs shall be prohibited for use of any type of storage. No storage is allowed under or within 10 ft of exterior stairs.
FIRE EXTINGUISHERS
❑4A Provide service or inspection by a state licensed company for all fire extinguisher annually.
❑4B Extinguishers are required to be properly mounted along an exit access with the top no higher than 5 feet.
❑4C Fire extinguisher(s) required. Provide extinguisher(s) of a 2A10BC minimum rating per NFPA 10.
trA GEf RALANDSTORAGE
SA Compressed gas cylinders/tanks shall be stored, appropriately secured, and identified with the produq na
❑SB Fir Systems n d cp1rrectio�� Hood cleaning due 3/2123, suppression due 1/1/21 xeU
NOTES:C, C, �j�t1 F3'FT"-S?C Yl s\V75� �4
Recipient:
Inspector,
Compliant
Inspector: