HomeMy WebLinkAboutA - 24-14-ITB - Attachment B - 23162 SEBASTIAN AIRPORT HANGAR MEP S-SREVISION REFERENCE #
LIGHT DASHED INDICATES EXISTING FIXTURE OR DEVICE
DARK DASHED INDICATES EXISTING FIXTURE OR DEVICE RELOCATED
DARK SOLID INDICATES NEW FIXTURE OR DEVICE
HATCHED ITEMS INDICATES FIXTURE OR DEVICE TO BE REMOVED OR RELOCATED
NOT IN CONTRACT (N.I.C.)
ABV - ABBREVIATION
AC - AIR CONDITIONER
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AHU - AIR HANDLING UNIT
AP - ACCESS PANEL
AS - AIR SEPARATOR
BD - BYPASS DAMPER
BOP - BOTTOM OF PIPE
BHP - BRAKE HORSE POWER
BTUH - BRITISH THERMAL UNIT
CAP - CAPACITY
CD - CONDENSATE DRAIN
CFM - CUBIC FEET PER MINUTE
CH - CHILLER
CHP - CHILLED WATER PUMP
CHR - CHILLED WATER RETURN
CHS - CHILLED WATER SUPPLY
COMB - COMBINATION
CONN - CONNECTION
CONT - CONTINUE
CT - COOLING TOWER
CW - COLD WATER
CWP - CONDENSER WATER PUMP
CWS - CONDENSER WATER SUPPLY
CWR - CONDENSER WATER RETURN
CU - CONDENSING UNIT
DB - DRY BULB
DIA - DIAMETER
DG - DOOR GRILLE
DL - DOOR LOUVER
DN - DOWN
DP - DIFFERENTIAL PRESSURE
DWG - DRAWING
EA - EXHAUST AIR
EAT - ENTERING AIR TEMPERATURE
EDH - ELECTRIC DUCT HEATER
EER - ENERGY EFFICIENCY RATIO
EF - EXHAUST FAN
EFF - EFFICIENCY
EG - EXHAUST GRILLE
ENT - ENTERING
ESP - EXTERNAL STATIC PRESSURE
ET - EXPANSION TANK
EWT - ENTERING WATER TEMPERATURE
EXP - EXPANSION
FA - FACE AREA
FCU - FAN COIL UNIT
FD - FIRE DAMPER
FLA - FULL LOAD AMPS
FLEX - FLEXIBLE
FPM - FEET PER MINUTE
FS - FLOOR SINK
FT - FEET
FV - FACE VELOCITY
GA - GAUGE
GPM - GALLONS PER MINUTE
HP - HORSE POWER
HB - HOSE BIBB
HR - HOUR
HW - HOT WATER
HWR - HOT WATER RETURN
HWS - HOT WATER SUPPLY
HZ - HERTZ
IN - INCHES
IW - INDIRECT WASTE
KEF - KITCHEN EXHAUST FAN
KSF - KITCHEN SUPPLY FAN
KW - KILOWATT
LAT - LEAVING AIR TEMPERATURE
LF - LINEAR FOOT
LWT - LEAVING WATER TEMPERATURE
LD - LINEAR DIFFUSER
LIQ - LIQUID
LP - LOOP PUMPS
MAU - MAKE-UP AIR UNIT
MAX - MAXIMUM
MBH - THOUSAND BTU PER HOUR
MCA - MINIMUM CIRCUIT AMPACITY
MECH - MECHANICAL
MIN - MINIMUM
MD - MOTORIZED DAMPER
NC - NORMALLY CLOSED
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
NO - NORMALLY OPEN
NOM - NOMINAL
NTS - NOT TO SCALE
OA - OUTSIDE AIR
OAU - OUTSIDE AIR UNIT
OC - ON CENTER
PD - PRESSURE DROP
PH - PHASE
PRV - PRESSURE REDUCING VALVE
PSI - POUNDS PER SQUARE INCH
PSIG - PSI GAUGE
PTAC - PACKAGED TERMINAL AIR CONDENSER
PVC - POLYVINYL CHLORIDE PIPE
QTY - QUANTITY
RA - RETURN AIR
REF - REFRIGERANT
RG - RETURN GRILLE
RPM - REVOLUTIONS PER MINUTE
RLA - RATED LOAD AMPS
RTU - ROOF TOP UNIT
SA - SUPPLY AIR
SEER - SEASONAL ENERGY EFFICIENCY RATING
SEN - SENSIBLE
SD - SMOKE DAMPER
SP - STATIC PRESSURE
SWD - SIDEWALL DIFFUSER
SWR - SIDEWALL RETURN
T - THERMOSTAT
TEMP - TEMPERATURE
TG - TRANSFER GRILLE
TSH - TOTAL SENSIBLE HEAT
TSP - TOTAL STATIC PRESSURE
TYP - TYPICAL
UC - UNDER CUT
UG - UNDER GROUND
UON - UNLESS OTHERWISE NOTED
VAV - VARIABLE AIR VOLUME
VLV - VALVE
VSD - VARIABLE SPEED DRIVE
WB - WET BULB
ZD - ZONE DAMPER
∆T - CHANGE IN TEMPERATURE
∆P - CHANGE IN PRESSURE
ALL WORK SHALL BE IN COMPLIANCE WITH THE FOLLOWING CODES, BUT NOT LIMITED TO:
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - BUILDING (FBCB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - EXISTING BUILDING (FBCEB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ACCESSIBILITY (FBCA)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ENERGY CONSERVATION (FBCEC)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - MECHANICAL (FBCM)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - PLUMBING (FBCP)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - FUEL GAS (FBCFG)
8TH EDITION OF THE 2023 FLORIDA FIRE PREVENTION CODE (FFPC)
NFPA 70 - 2020 NATIONAL ELECTRICAL CODE (NEC)
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
A.THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY
THIS WORK BEFORE SUBMITTING PROPOSAL SO AS TO BECOME FAMILIAR WITH EXISTING WORK. SUBMISSION OF A
PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR
LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OR BY DIFFICULTIES ENCOUNTERED WILL NOT BE
RECOGNIZED. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT
BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN EQUIPMENT
ROUTING AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE
NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS CONTRACT. IT IS
ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY
DIMENSIONS OF ALL EXISTING CONDITIONS, PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
B.ALL DEVICES AND EQUIPMENT NOT SHOWN AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS
OTHERWISE NOTED. INSTALL AS REQUIRED TO MAINTAIN CONTINUITY TO EXISTING DEVICES AND EQUIPMENT THAT
ARE TO REMAIN.
C.ALL EQUIPMENT AND MATERIAL REMOVED AND NOT REUSED SHALL BE TURNED OVER TO THE OWNER OR AT THE
OWNERS REQUEST LEGALLY DISPOSED OF BY THE CONTRACTOR.
D.ALL HVAC DEVICES, EQUIPMENT, DUCTWORK, ETC., THAT ARE REMOVED SHALL BE REMOVED AS DIRECTED BY THE
OWNER/ENGINEER, AND CEILING OR WALL SHALL BE PATCHED TO MATCH EXISTING OR NEW FINISH. ALL PATCHES
SHALL BE PATCHED OR PAINTED AS DIRECTED BY ARCHITECTURAL DRAWINGS.
E.ALL EXISTING HVAC EQUIPMENT, DUCTWORK, DEVICES, ETC., IS NOT SHOWN. IT IS THE CONTRACTORS
RESPONSIBILITY TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND INCLUDE IN HIS BID THE
REMOVAL OF ALL EQUIPMENT, DUCTWORK, DEVICES, ETC., THAT IS NOT BEING REUSED BACK TO ITS SOURCE.
F.ALL CONCRETE, WALL PATCHING, CEILING REPAIR, AND OTHER GENERAL WORK REQUIRED FOR INSTALLING THE HVAC
SYSTEMS AND TO REPAIR TO "LIKE NEW CONDITION" TO BE PROVIDED AND INSTALLED BY THE CONTRACTOR.
G.PROVIDE AND INSTALL ANY ADDITIONAL HANGERS/SUPPORTS REQUIRED TO ACCOMMODATE ANY EQUIPMENT
RELOCATIONS.
H.COORDINATE ALL CEILING MOUNTED DEVICES WITH ARCHITECTURAL REFLECTED CEILING AND WORK OF ALL OTHER
TRACES.
I.ITEMS NOTED AS EXISTING TO BE REMOVED SHALL BE REMOVED COMPLETELY. REMOVAL SHALL INCLUDE ALL
DEVICES, PIPING, HANGERS, SUPPORTS, ETC.
M-1
EED
ME
C
H
A
N
I
C
A
L
L
E
G
E
N
D
,
N
O
T
E
S
,
&
S
P
E
C
I
F
I
C
A
T
I
O
N
S
JMF
DAD
MECHANICAL SYMBOLS LEGEND, NOTES, AND SPECIFICATIONS
HVAC LEGEND HVAC PIPING LEGEND GENERAL NOTES MECHANICAL SPECIFICATIONS
SHEET NOTE CALLOUT
ABBREVIATIONS
CODE COMPLIANCE REQUIREMENTS
GENERAL DEMOLITION NOTES
SCOPE OF WORK:
CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS AS REQUIRED TO PROVIDE A COMPLETE AND OPERATIONAL
HVAC SYSTEM AS INDICATED ON THE DRAWINGS. CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH ALL OTHER
TRADES. CHANGES TO THE DESIGN BY THE CONTRACTOR WILL RESULT IN ADDITIONAL DESIGN COST AT CONTRACTORS
EXPENSE.
SPECIAL PROVISIONS:
ALL WORK SHALL BE IN COMPLIANCE WITH THE 2023 FLORIDA BUILDING CODE (8TH EDITION), 2023 FLORIDA BUILDING
CODE - MECHANICAL (8TH EDITION), 2023 FLORIDA BUILDING CODE - PLUMBING (8TH EDITION), 2023 FLORIDA FIRE
PREVENTION CODE (8TH EDITION), 2023 FLORIDA BUILDING CODE - ENERGY CONSERVATION (8TH EDITION) FOR BUILDING
CONSTRUCTION, 2020 NATIONAL ELECTRIC CODE (NEC), UNITED LABORATORIES (UL), AND THE ORDINANCES AND
REGULATIONS OF THE LOCAL AUTHORITY HAVING JURISDICTION.
SHOP DRAWINGS:
BEFORE PURCHASE OR FABRICATION OF EQUIPMENT AND WITHIN 30 DAYS OF AWARD OF GENERAL CONTRACT,
CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER FOR APPROVAL, 3 COPIES OF SHOP DRAWINGS FOR ALL
DUCTWORK AND HVAC EQUIPMENT AND MATERIALS. SHOP DRAWINGS SHALL INDICATE WORKING AND ERECTION
DIMENSIONS, ELECTRICAL CHARACTERISTICS (VOLTS, PHASE AND AMPS), LOCATION AT WHICH MATERIALS AND
EQUIPMENT ARE TO BE INSTALLED AND OTHER ESSENTIAL DATA. PARTIAL OR INCOMPLETE SUBMITTALS WILL NOT BE
ACCEPTED. ANY MATERIAL USED WITHOUT APPROVAL WILL BE REJECTED. PROVIDE SUBMITTALS ON ALL ITEMS EXCEPT
PIPING. SUBMIT SHOP DRAWINGS TO ELECTRICAL CONTRACTOR FOR APPROVAL AND COORDINATION. A COMPLETE HVAC
DUCT LAYOUT INCLUDING AIR DISTRIBUTION DEVICES SHALL BE SUBMITTED TO ENGINEER FOR REVIEW PRIOR TO
CONSTRUCTION.
MATERIALS:
MATERIALS, UNLESS OTHERWISE NOTED, SHALL BE NEW, FREE OF DEFECTS AND IN ACCORD WITH FOLLOWING
SCHEDULES AND PARAGRAPHS. THE APPROVAL OF ANY MATERIALS WILL NOT BE CONSIDERED AS ACCEPTANCE OF WORK
WHERE INSTALLED IF SUCH MATERIALS PROVE DEFECTIVE. WHERE NO SPECIFIC WEIGHTS OR GRADES ARE SPECIFIED,
MATERIALS SHALL BE OF THE GENERALLY ACCEPTED STANDARD WEIGHT AND GRADE.
DUCTWORK (FIBERGLASS):
THE HEATING AND AIR CONDITIONING DUCTWORK SHALL BE OWENS CORNING TYPE 475-FR, 1-1/2" THICK FIBERGLASS
DUCT (MIN R-VALUE OF 6) OR APPROVED EQUAL. THE DUCT SYSTEM, INCLUDING BOARD, VAPOR BARRIER, TAPES AND
ADHESIVES, SHALL BE UL LISTED AND LABELED CLASS 1 AIR DUCT. DUCT SHALL BE INSTALLED PER THE STANDARD OF
SMACNA-10 IN CHAPTER 15 OF FBCM. EXHAUST DUCT SHALL BE GALVANIZED.
DUCTWORK (GALVANIZED STEEL):
THE HEATING AND AIR CONDITIONING DUCTWORK SHALL BE G-90 GALVANIZED STEEL PAINTED, w/ BLANKET INSULATION
(MIN. R-6). EXHAUST DUCT SHALL BE GALVANIZED. PROVIDE FLEX DUCT TO AIR DEVICE WHERE SHOWN (NO MORE THAN
6'-0" LONG). ALL DUCTWORK PENETRATING FIRE-RATED WALLS SHALL HAVE A FIRE DAMPER. THE USE OF R-6 DUCTBOARD
MAY BE USED AS AN ALTERNATE (OWNER OPTION).
AIR DISTRIBUTION OUTLETS:
GRILLES, REGISTERS, AND DIFFUSERS SHALL REQUIRE ADC, ARI, AND AMCA COMPLIANCE. BORDER STYLES AND
FINISHES SHALL BE COMPATIBLE WITH ADJACENT CEILING SYSTEMS, AND CONSTRUCTED OF MATERIALS AND
COMPONENTS AS REQUIRED FOR A COMPLETE INSTALLATION. SUPPLIER/MANUFACTURER SHALL VERIFY EACH DEVICE
FOR A MAXIMUM NECK VELOCITY OF 500 FPM AND NC-30.
REFRIGERATION:
REFRIGERANT PIPING SHALL BE ACR COPPER TUBING, WITH WROUGHT COPPER FITTINGS IN CONFORMANCE WITH ASTM
B280.
A.JOINTS IN COPPER TUBE (REFRIGERANT SERVICE) - CUT SQUARE, BURR, CLEAN FITTING AND TUBE TO CUP DEPTH
OF FITTING APPLY THIN FILM OF BRAZING FLUX TO TUBE END AND FITTING. USE SILVER SOLDER AND
OXYGEN-ACETYLENE EQUIPMENT ONLY IN MAKING JOINTS. PURGE WITH NITROGEN WHEN HEATING.
B.PIPING SHALL BE SIZED AND INSTALL PER THE HEAT PUMP EQUIPMENT MANUFACTURER'S WRITTEN INSTRUCTION.
C.SUCTION LINES SHALL BE INSULATED CONTINUOUSLY WITH EXTERIOR EXPOSED SURFACES TREATED PER
MANUFACTURER'S RECOMMENDATIONS. INSULATION SHALL BE ARMAFLEX OR EQUAL.
D.REFRIGERANT PIPING EXPOSED TO EXTERIOR SHALL BE INSULATED AND WRAPPED WITH ALUMINUM JACKET WITH A
MINIMUM 2" OVERLAPS. JACKET SHALL BE SECURED USING BANDS AND SEALS.
CONDENSATE DRAIN LINE:
CONDENSATE DRAIN LINES SHALL BE PROVIDED FOR AIR HANDLING UNITS. DRAIN LINES SHALL BE SCHEDULE 40 PVC.
A.DRAIN LINES SHALL BE GRADED IN THE DIRECTION OF FLOW WITH A SLOPE OF 1 4" PER FOOT.
B.WATER SEALS SHALL BE PROVIDED IN THE CONDENSATE DRAIN FROM UNIT. THE DEPTH OF SEAL SHALL BE EQUAL
TO THE TOTAL STATIC PRESSURE RATING OF THE UNIT TO WHICH THE SEAL IS CONNECTED. WATER SEALS SHALL BE
CONSTRUCTED TO TWO TEES AND AN APPROPRIATE U-BED WITH THE OPEN END TO EACH TEE PLUGGED,
HANDTIGHT.
C.ROUTE DRAIN LINE INTO OUTSIDE FRENCH DRAIN OR SPLASH BLOCK.
TEST AND BALANCE
PROVIDE A COMPLETE TEST AND BALANCE REPORT AND SUBMIT TO ENGINEER FOR REVIEW. T&B FIRM MUST BE NEBB
OR AABC CERTIFIED.
READINGS SHALL INCLUDE BUT SHALL NOT BE LIMITED TO THE FOLLOWING:
·SUPPLY AIR CFM
·RETURN AIR CFM
·STATIC PRESSURE
·EXHAUST AIR CFM
*ANY CHANGES TO THESE DOCUMENTS BASED ON CONTRACTOR REQUESTED REVISIONS SHALL BE CONSIDERED
ADDITIONAL SERVICES.
#
1.VERIFY THAT ALL EQUIPMENT, AS SHOWN ON THESE DRAWINGS, WILL NOT CONFLICT WITH ANY DRAINS, SCUTTLES,
JOINTS, VENTS, PIPING OR OTHER EQUIPMENT PRIOR TO INSTALLATION.
2.EQUIPMENT SUPPLIER SHALL PROVIDE COMPLETE INFORMATION AND COOPERATE WITH THE OWNER'S
REPRESENTATIVE AS REQUIRED FOR PROJECT COMPLETION AND COORDINATION.
3.CONTRACTOR SHALL ADMINISTER AND SUBMIT ALL DRAWINGS FOR PERMITTING.
4.ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 10'-0" FROM ANY EXHAUST FAN, GAS OR PLUMBING VENT.
5.PROVIDE VIBRATION ISOLATION DEVICES AND FLEXIBLE CONNECTIONS TO ALL MOVING MACHINERY.
6.ALL PIPE AND DUCTWORK DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
7.COORDINATE WITH ALL OTHER TRADES, ALL REQUIRED OPENINGS AND ROOF PENETRATIONS. ALL REQUIRED
OPENINGS IN FOUNDATIONS, FLOORS, WALLS AND ROOF SHALL BE MADE AND INSTALLED INTO THE STRUCTURE WITH
THE USE OF SLEEVES, CURBS, ETC.
8.PROVIDE SHOP DRAWINGS FOR ALL HVAC EQUIPMENT AND MATERIALS.
9.CONTROL PANELS AND REMOTE SENSORS SHALL BE LOCATED GENERALLY AS SHOWN. EXACT LOCATIONS SHALL BE
FIELD COORDINATED TO AVOID INTERFERENCE WITH WALL MOUNTED WORK.
10.FURNISH AND INSTALL 4" HIGH BLACK NAMEPLATES FOR ALL EQUIPMENT.
11.FIELD VERIFY ALL EXISTING SERVICES PRIOR TO START OF CONSTRUCTION.
12.REMOVE EXISTING CEILINGS, GRID, CEILING DEVICES, ETC., TO INSTALL NEW HVAC SYSTEMS. REINSTALL OR
PROVIDE NEW CEILING GRID AND TILE, TO MATCH EXISTING CONDITIONS. REINSTALL EXISTING CEILING DEVICES.
13.CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF EXISTING CEILING, WALLS, SLABS, ETC. TO INSTALL
NEW SYSTEM. MINIMIZE SAW CUTTING OF WALLS, SLABS, ETC. PATCH AND REPAIR ALL SURFACES IMPACTED BY
CONSTRUCTION. PAINT ALL SURFACE TO MATCH EXISTING FINISH.
DESIGN CRITERIA
DESIGN TEMPERATURES:
OUTDOOR AIR:
SUMMER:95°F DB/80°F WB
WINTER:30°F DB
INSIDE AIR:
SUMMER:75°F DB/60% RH
WINTER:72°F DB
NOTES:
THE DESIGN CRITERIA ABOVE IS BASED ON ASHRAE STANDARD 62.1. ANY CHANGES TO THIS OCCUPANCY OR FLOOR PLAN
WILL REQUIRE FURTHER REVIEW AND MODIFICATIONS TO THIS VENTILATION SYSTEM.
POINT OF CONNECTION
POINT OF DISCONNECT
MISCELLANEOUS
(150)
EXISTING DIFFUSER WITH CFM'S
CONTROL VALVE
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CONDENSATE
CONNECTION, BOTTOM
CONNECTION, TOP
CWS
CWR
CHECK VALVE
STRAINER
BUTTERFLY VALVE
CALIBRATING BALANCING VALVE
GATE VALVE OR BALL VALVE
UNION
CD
THERMOMETER
FLOW DIRECTION
CHR CHILLED WATER RETURN
CHILLED WATER SUPPLYCHS
HOT WATER SUPPLYHWS
NEW CFM
EXISTING
CFM
REFRIGERANT PIPINGREF
SWR
SWD
20"Ø
T
ROUND SPIRAL
MANUAL BALANCING DAMPER
FIRE & SMOKE DAMPER (WITH ACCESS PANEL)
FIRE DAMPER (WITH ACCESS PANEL)
90° ELBOW W/TURNING VANES
ROUND DIFFUSER
SIDE WALL RETURN
SIDE WALL DIFFUSER
CEILING DIFFUSER, ROUND NECK (CEILING DIFFUSERS ARE 4-WAY THROW UON)
TEMPERATURE SENSOR
MOTORIZED CONTROL DAMPER
THERMOSTAT/TEMPERATURE SENSOR
PRESSURE SENSOR
BACKDRAFT DAMPER
CEILING MOUNTED ACCESS DOOR
RADIUS ELBOW W/O TURNING VANES
OUTSIDE AIR LOUVER
OUTSIDE AIR ROOF INTAKE
ELECTRIC DUCT HEATER
ITEM(S) TO BE REMOVED
DOUBLE LINE DUCTWORK, FIRST DIMENSION IS SIDE SHOWN.20x12
FLEX DUCTWORK
VARIABLE AIR VOLUME (VAV) BOX W/ HEAT
BD
P
TS
M
SINGLE LINE DUCTWORK, FIRST DIMENSION IS SIDE SHOWN.
20x12
EDH-#
OAL
RI-#
DUCT UP TO OUTSIDE AIR ROOF INTAKE ABOVERI-#
EXHAUST AIR ROOF VENTRV-#
DUCT UP TO EXHAUST AIR ROOF VENT ABOVERV-#
ROOF TOP EXHAUST FANEF-#
DUCT UP TO ROOF TOP EXHAUST FAN ABOVEEF-#
CEILING RETURN GRILLE WITH SQUARE CONNECTION
CEILING RETURN GRILLE WITH ROUND CONNECTION
CEILING EXHAUST GRILLE
EXHAUST FANEF-#
H HUMIDISTAT/HUMIDITY SENSOR
R
S
PHOTOELECTRIC DUCT SMOKE DETECTOR
R=RETURN S=SUPPLY
SMOKE DAMPER (WITH ACCESS PANEL)
20"Ø DOUBLE LINE ROUND DUCTSOCK
20"Ø
SINGLE LINE ROUND DUCTSOCK
VARIABLE AIR VOLUME (VAV) BOX W/ NO HEAT
ZONE DAMPER
IN-LINE EXHAUST FAN
CONDENSER UNIT
AC-#
VERTICAL AC UNIT
HORIZONTAL AC UNIT
HORIZONTAL HEAT PUMP UNIT
PACKAGED ROOFTOP OR GROUND MOUNTED AC UNIT
EQUIPMENT TAG
SEQUENCE OF OPERATION
PROVIDE INDIVIDUAL ROOM LED PROGRAMMABLE THERMOSTATS THAT SHALL MAINTAIN ROOM SET POINTS.
1.AIR HANDLER FAN SHALL START AND STOP ON COMMAND FROM THERMOSTAT BASED ON TIME OF DAY SCHEDULE.
2.LOCAL OVERRIDE CONTROL WILL START FAN AND PERMIT IT TO RUN FOR A PREDETERMINED INTERVAL.
3.OUTSIDE AIR DAMPER SHALL OPEN AND SHALL BE CONTROLLED BY A MOTORIZED DAMPER INTERLOCKED WITH THE
COMPRESSOR.
4.ON A RISE OF RETURN OR SPACE AIR TEMPERATURE FROM 75°F SETPOINT (ADJUSTABLE), THE CONTROLLER SHALL
ENERGIZE THE UNIT'S COMPRESSOR TO MAINTAIN 57°F SUPPLY LEAVING AIR TEMPERATURE SETPOINTS.
5.SPACE AIR TEMPERATURE SETPOINT SHALL BE SET BY THE OWNER AND SHALL BE ADJUSTABLE.
6.THE CONTROLLER SHALL STAGE ONE COMPRESSOR AT A TIME. IF TEMPERATURE INCREASES, THE SECOND
COMPRESSOR WILL BE STAGED ON (IF DUAL COMPRESSOR IS FURNISHED)
7.IN THE WINTER MONTHS, THE UNIT'S HEATERS SHALL BE STAGED ON TO MAINTAIN 68°F.
8.IF HUMIDITY INCREASES ABOVE 60%. THE UNITS SHALL ENERGIZE THE COMPRESSOR TO MAINTAIN A COLD COIL.
ZD-#
VAV-#
VAV-#
EF-#
CU-#
AC-#
AC-#
HP-#
RTU-#
DUCTWORK/SUPPORTS
ELECTRIC DISCONNECTS
CONTROLS
PIPING
INSULATION
EXHAUST FANS
DIFFUSERS/GRILLES
ALL HVAC EQUIPMENT
ITEM COPY FOR
OWNER
PRODUCT DATA SHOP
DRAWINGS
TEST
REPORTS
COORDINATION
DRAWINGS
WIRING
DIAGRAMS
O & M
MANUAL
SHOP DRAWING SUBMITTALS
1 2 3 4 1 2 1 2 1 2 1 2 1 2
NOTES:
1- FOR REVIEW
2- FOR RECORD
3- COLOR SELECTION
4- SAMPLE
NOTE:
FOR ALL MATERIALS FOR CONSTRUCTION, INSTALLATION REQUIREMENTS AND
TESTING REQUIREMENTS, REFER TO CONTRACT SPECIFICATIONS.
CONTRACTOR SHALL SUBMIT ALL ITEMS UNDER ONE SUBMITTAL THAT REFERENCES
DDC PROJECT NUMBER. NO PARTIAL SUBMITTALS WILL BE ACCEPTED. ALL
SUBMITTALS SHALL BE EMAILED TO INFO@DDC-ENGINEERS.COM .
REVIEW
2
A
A
A.8
A.8 B.8
A.8
3
4
5
6
MGMT.
OFFICE #1
107
MGMT.
OFFICE #2
108
CONF. RM.
109
RECEPT.
AREA
110
TRAINING #1
112
CORR.
111
TRAINING #2
113
TRAINING #3
114
TRAINING #4
115
FOYER
117
CORR.
118
UTIL.
RM.
119
R.R.
120
R.R.
121
PILOT
BRIEFING RM.
123
CORR.
122
RECEPT.
OFFICE
116
225
225
325
125
125
100
125
100
150
650
200
12
"
x
1
2
"
14
"
x
1
2
"
12
"
x
1
2
"
14
"
x
1
2
"
AC-1N
AC-2N
22"x12"
22"x12"
18
"
x
1
2
"
14
"
x
1
2
"
12
"
x
1
2
"
12
"
x
1
2
"
14
"
x
1
2
"
18
"
x
1
2
"
EX. EFEX. EF
CU-1N
CU-2N
22
"
x
1
2
"
22
"
x
1
2
"
T
AC-2N
TYP.3
TYP.2
EX. EF
125
125
125
700
350
350
50
100
150
T
AC-1N
8"Ø
M
M
3
4
4
6
5
7
7
7 TYP.
10
8
50
75
TYP.
TYP.
125
11
D
D C B
A
A
10
9
C.2A.9
SIMULATOR
AREA
100
OFFICE
#1
101
OFFICE
#2
102
BREAKROOM
103
UTILITY
ROOM
104
R.R.
105
R.R.
106 12"x10"
SWD
300
TYP.
CFM
300
CFM
300
CFM
300
CFM
12"x12"20"x12"
225
200
EX. EF
EX AC-1S
50
50EX CU-1S
75
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
M-2
EED/SBH
ME
C
H
A
N
I
C
A
L
P
L
A
N
JMF
DAD
#PLAN NOTES
1.SIZE FLEX DUCT BASED ON SCHEDULE PROVIDED.
2.INSULATE BACK OF ALL DIFFUSERS.
3.MOUNT THERMOSTAT AT 48" ABOVE FINISHED FLOOR.
4.SUSPEND AC UNIT FROM STRUCTURE. SEE DETAIL.
5.PROVIDE O.A. WALL CAP.
6.PROVIDE MOTORIZED AND MANUAL DAMPER IN O.A. DUCT.
7.ROUTE REFRIGERANT PIPING OVERHEAD TO CONDENSER UNIT.
8.ROUTE 3 4" CONDENSATE DRAIN TO EXTERIOR GREEN AREA OR DRYWELL.
9.MOUNT CONDENSER UNIT ON 4" PAD AND ANCHOR TO PAD.
10.ROUTE REFRIGERANT PIPE DOWN WALL. PROVIDE 18 GAUGE PAINTED SHEET METAL
ENCLOSURE. SEAL ALL OPENINGS IN ENCLOSURE.
NORTH BAY 3/16" = 1'-0"
MECHANICAL PLAN
SOUTH BAY 3/16" = 1'-0"
MECHANICAL PLAN
NOTE:
1.RETURN AIR CFMS FOR GRILLES SHALL MATCH SUPPLY AIR CFMS FOR THAT ROOM.
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
M-3
EED/SBH
ME
C
H
A
N
I
C
A
L
S
C
H
E
D
U
L
E
S
A
N
D
D
E
T
A
I
L
S
JMF
DAD
AIR BALANCE
NORTH BAY
OUTSIDE AIR
AC-1N = 150 CFM
AC-2N = 150 CFM
TOTAL OUTSIDE AIR = 300 CFM
EXHAUST AIR
EX. EF(3)= 225 CFM
TOTAL EXHAUST AIR = 225 CFM
BUILDING IS POSITIVE = 75 CFM
AC SPLIT SYSTEM SCHEDULE
ESPCFM
NOMINAL MANUFACTURER
NOTES:1.PROVIDE MOTORIZED OUTSIDE AIR INTAKE
DAMPER FOR THE OA DUCT.
2.INSTALL AND ANCHOR CONDENSER UNIT TO
STRUCTURE ( SLAB).
3.MIN. SEER OF 16.0
MARK
OUTDOOR
INDOOR/O.A.
CFM
COOLING CAPACITY
AMB.
TEMP
TOT
MBH
SENS
MBH
ENT
DB WB
ENT
ELECTRICAL DATA (OUTDOOR UNIT)
NO
COMP
COMP
RLA(EA)FAN
NO
FLA(EA)
FAN
HP
FAN
PHASE
VOLT/
ELECTRICAL DATA (INDOOR UNIT)
FAN
HP
KW
HEAT STAGE VOLT/
PHASE TONS
NOMINAL
4.COORDINATE INSTALLATION OF SMOKE
DETECTORS WITH DIV. 16 (NOT REQ'D IF 2000
CFM OR LESS.
5.PROVIDE VIBRATION ISOLATIONS.
6.PROVIDE 410A REFRIGERANT.
7.PROVIDE SINGLE POINT ELECTRICAL CONNECTION
WITH DISCONNECT.
8.PROVIDE 1" PLEATED FILTERS.
9.PROVIDE 5 YEAR WARRANTY.
10.PROVIDE CONDENSER COIL GUARDS.
11.PROVIDE PROGRAMMABLE THERMOSTAT.
12.BALANCE UNITS BASED ON AIRFLOW RATES SHOWN ON DRAWINGS.
13.PROVIDE VARIABLE SPEED AIRHANDLER WITH HUMIDISTAT
CONTROL.
14.PROVIDE UNLOADING COMPRESSOR. (MIN. 2 STAGES)
15.PROVIDE 30" WIDE AND 30" DEEP CLEAR SPACE ON SERVICE SIDE
OF EQUIPMENT.
MCA/
MOCP
MCA/
MOCP
EXHAUST FAN SCHEDULE
MOTORMARKTYPECFMESPWATTSRPM HP DRIVE TYPE FAN SERVICE SONES
MAX
PHASE
VOLT /CONTROL MANUFACTURER / MODEL NOTES
PROVIDE THE FOLLOWING: DISCONNECT SWITCH, VIBRATION ISOLATORS, BACKDRAFT DAMPER, SPEED CONTROL
EX. EF CEILING 70 0.25 20 --DIRECT RESTROOMS 5 115/1 SWITCH EXISTING SEE BELOW
N.T.S.
TYPICAL DUCT /
DIFFUSER DETAIL
AIR FLOW
DUCT SUPPORT
DAMPER OPERATOR SHALL
BE ACCESSIBLE. PROVIDE
EXTENSION THRU INSULATION
PROVIDE SADDLE
SUPPORT
SUPPORT FROM
STRUCTURE
INSULATED
FLEX DUCT
SPIN-IN FITTING WITH
SCOOP AND VOLUME
DAMPER
DUCT CLAMP
SUPPORT FROM
STRUCTURE
SUPPLY AIR
DUCT
DIFFUSER
CEILING
INSULATE BACK OF ALL AIR
DISTRIBUTION DEVICES
M3
N.T.S.
CONDENSER UNIT DETAIL
WALL MOUNTED
DISCONNECT, NEMA 3R
UNIT ANCHORS
NOTES:
1.CONDENSERS LOCATED NEAR COASTAL WATERS SHALL BE COATED WITH
BRONZEGLOW OR HERESITE COIL COATING.
2.UNIT ANCHORS SHALL BE FLORIDA AND MIAMI/DADE PRODUCT APPROVED
AS MANUFACTURED BY MIAMI TECH, INC. (FL# FL19731-R-3) OR EQUAL.
INSTALL AS REQUIRED BY MANUFACTURER TO WITHSTAND WIND LOADS
OF 175 MPH. USE CARE AND DO NOT PUNCTURE COMPONENTS.
FIBER MESH CONCRETE AT 3000 PSI.
4" HIGH, MEASURED FROM HIGHEST
POINT OF GRADE.
EXTERIOR GRADE
20 GAUGE SHEET METAL
ENCLOSURE. PAINT TO MATCH
EXTERIOR. SEAL OPENINGS.
REFRIGERANT PIPING. MOUNT ON
WALL ON UNISTRUT SUPPORT.
SCREEN
M1
N.T.S.
INSULATED
PIPE HANGER DETAIL
M-D009
SIZES UP TO 3"
SINGLE
MULTIPLE
PIPE
PIPE SADDLE
(TYP.)
ALL INSULATION PASSES
THRU HANGER UNBROKEN LOCKNUT (TYP.)
UNISTRUT OR
ANGLE IRON
WASHER (TYP.)
PIPE SADDLE
(18 GA., 18" LONG)
ATTACH TO
STRUCTURE
CONTINUOUS
THREADED ROD
U-BOLT
PIPE INSULATION
PIPE
M2
~
5" DRAINABLE
SECURE TO WALL
LINTEL
DUCT
BIRDSCREEN
LOUVER (MIN.)
LOUVER FRAME
EXISTING WALL
CAULK ALL
AROUND
CAULK
RAIN SILL
N.T.S.
LOUVER DETAIL
TYPICAL WALLM4
N.T.S.
CONDENSATE DRAIN
P-TRAP DETAIL
NOTE:
1.FILL TRAP MANUALLY ON INITIAL START-UP.
2.PIPE SIZE SHALL NOT BE LESS THAN DRAIN PAN CONNECTION SIZE.
3.A = 11
2 TIMES FAN SUCTION S.P.
B = 12" PLUS FAN DISCHARGE S.P.
4.ALL CONDENSATE PIPING TO BE COPPER.
5.INSULATE ALL DRAIN LINES WITH 3 4" ARMAFLEX
B
A
SLOPE TO
DRAIN
DRAIN PAN
CASING SLEEVE
AIR
HANDLER
UNIT
UNION
THREADED CAP WITH 1 2"Ø
HOLE DRILLED IN TOP,
HAND TIGHTENED.
THREADED CAP,
HAND TIGHTENED
12" EXTENSION PIPE
WITH THREADED CAP
AT END
FLOAT SWITCH IN
SECONDARY DRAIN LINE
TO DISABLE AHU SHOULD
SECONDARY DRAIN LINE
ACCUMULATE WATER.
M5
AIR DISTRIBUTION DEVICE SCHEDULE
MANUFACTURER / MODEL
REMARKS:1.PROVIDE OPPOSED BLADE VOLUME DAMPERS.
2.CONTRACTOR SHALL COORDINATE GRILLES, DIFFUSERS AND REGISTER'S BORDER TYPES WITH CEILING,
WALLS, EQUIPMENT ETC.
3.PROVIDE ALL ALUMINUM CONSTRUCTION.
MARK NC
MAX
SIZE (IN.)
NECK FLEX
DIAM. (IN.)REMARKSTYPECFM
RANGE
25 6
825
1025
1225
1425
24x24
12x12
0-800 25 20x20 -
-48x2425801-3000
SWD
SWR
401-750
0-400 -12x1225
-18x1825DG
DIFFUSERS
SUPPLY
RETURN
GRILLE
SIDEWALL
DIFFUSER
SIDEWALL
RETURN
DOOR
GRILLE 3
1,2,3
1,2,3
1,2,3
1,2,3
1.ALL GRILLES SHALL BE FULL FACE OF MODULE. ALL LAY-IN CEILING RETURN MODULES SHALL BE 24"x24"
WITH 20"x20"x1" FILTER
2.INSULATE THE BACK OF ALL SUPPLY AND RETURN AIR DEVICES.
3.PROVIDE BORDER TYPE 1 FOR LAY-IN CEILINGS, AND BORDER TYPE 3 FOR GYPSUM BOARD CEILINGS.
4.PROVIDE 1" PLEATED FILTER.
5.THE NUMBER ADJACENT TO THE FIXTURE INDICATES AIR FLOW (CFM).
NOTES:
-25 -DWGS
SEE
DWGS -25-SEE
0-100
101-200
201-300
301-400
401-600
6"Ø
8"Ø
10"Ø
12"Ø
14"Ø
1001-1500 25 1818"Ø
601-1000 162516"Ø
GREENHECK
XG-5500-APD
GREENHECK
XG-RH
GREENHECK
XG-H4004
GREENHECK
XG-RH
GREENHECK
XG-DGDF
PROVIDE LOUVERS AS MANUFACTURED BY GREENHECK
MODEL EVH-501D. LOUVER SHALL BE 5" DRAINABLE ALL
ALUMINUM. PAINT TO MATCH EXISTING FINISH. ALL
LOUVERS TO MEET CURRENT MIAMI-DADE HURRICANE
STANDARDS AND FLORIDA BUILDING CODE. SIZE LOUVER
AS SHOWN BELOW (IF NOT SPECIFIED ON DRAWINGS).
CFM LOUVER SIZE
0-300
501-1000
1001-1500
1501-2000
24"X16"
36"X16"
48"X16"
NOTE: PROVIDE REMOVABLE INSECT SCREEN ON BACK OF
LOUVER.
72"X16"
LOUVER
SCHEDULE
301-500 24"X16"
SCHEDULE
CFM DUCT SIZE
0-100 6"Ø
8"Ø101-200
10"Ø201-300
12"Ø301-400
14"Ø401-600
18"Ø1001-1500
20"Ø1501-2000
SIZE BOTH SUPPLY AND RETURN BASED UPON
AIRFLOWS ABOVE.
16"Ø601-1000
TRANSFER DUCT SIZE
9"Ø
12"Ø
16"Ø
18"Ø
22"Ø
28"Ø
30"Ø
24"Ø
FLEX DUCT
SD
FLOAT SWITCH
BEYOND AHU
EXTEND 4"
COIL SECTION
SECTION
FILTER
CONNECTION (TYP)
FLEXIBLE DUCT
AIR DUCT
OUTSIDE
DAMPER
RETURN AIR W/
AIR
SUPPLY
DRAIN PAN
W/ DAMPER
N.T.S.
HORIZONTAL AIR
HANDLING UNIT
P-TRAP
PROVIDE NEOPRENE PAD
PRESSURE TREATED BLOCK
BETWEEN BLOCK AND UNIT
M6
EX. AC-1S/CU-1S 1800 175 .5 95 80 67 41.9 58.0 1 28.8 1 1.9 1/4 208/1 32/50 3/4 9.0 1 208/1 54/60 5 TRANE/CARRIER/LENNOX
(PEOPLE/1000 SQ.FT.)
OCCUPANCY DENSITY
OUTDOOR AIR SCHEDULE
UNIT TAG
PERSON
CFM/
FBC-MECHANICAL TABLE 403.3.1.1
(SQ. FT)
AREA
(# OF PEOPLE)
ZONE MAX OCCUPANCY
AREA
CFM/
EX. AC-1S OFFICE 5 5 0.06190110 164
USE
ZONE
PROVIDED
OA CFMPER SEC.
OA CFM
403.2 *O.A. CFM
REQUIRED
TOTAL
175
AC-1N/2N OFFICE 5 5 0.06287215 247 300
AC-1N/CU-1N 1600 150 .5 95 80 67 35.9 49.5 1 19.8 1 1.4 1/6 208/1 26/40 1/2 9.0 1 208/1 54/60 4 TRANE/CARRIER/LENNOX
AIR BALANCE
SOUTH BAY
OUTSIDE AIR
AC-1S = 175 CFM
TOTAL OUTSIDE AIR = 175 CFM
EXHAUST AIR
EX. EF(2)= 150 CFM
TOTAL EXHAUST AIR = 150 CFM
BUILDING IS POSITIVE = 25 CFM
COOLING/HEATING LOAD SUMMARY
OUTDOOR INDOOR COOLING (MBH)
ZO
N
E
U
N
I
T
#
AR
E
A
S
Q
U
A
R
E
F
E
E
T
TO
T
A
L
H
E
A
T
I
N
G
WI
T
H
O
U
T
I
S
D
E
A
I
R
(M
B
H
)
GR
A
I
N
S
W
A
T
E
R
(D
I
F
E
R
E
N
C
E
)
DR
Y
B
U
L
B
(
D
B
)
WE
T
B
U
L
B
(
W
B
)
DR
Y
B
U
L
B
(
D
B
)
RE
L
A
T
I
V
E
HU
M
I
D
I
T
Y
(
%
R
H
)
TO
T
A
L
S
E
N
S
I
B
L
E
TO
T
A
L
L
A
T
E
N
T
TO
T
A
L
W
I
T
H
OU
T
S
I
D
E
A
I
R
AC-1N 1600 95 80 75 60 35.9 13.6 49.5 31 14.2
EX. AC-1S 1800 95 80 75 60 41.9 16.1 58 30 16.2
NOTES:
-THIS SUMMARY IS BEING SUBMITTED IN ACCORDANCE WITH 2023 FLORIDA BUILDING CODE
(8TH EDITION), 2023 ENERGY CONSERVATION CODE (8TH EDITION), SECTION C403.2.1.
-SIZING METHOD USED: ASHRAE TRANSFER FUNCTION METHOD.
AC-2N/CU-2N 1600 150 .5 95 80 67 35.9 49.5 1 19.8 1 1.4 1/6 208/1 26/40 1/2 9.0 1 208/1 54/60 4 TRANE/CARRIER/LENNOX
AC-2N 1600 95 80 75 60 35.9 13.6 49.5 31 14.2
REVISION REFERENCE #
LIGHT DASHED INDICATES EXISTING FIXTURE OR DEVICE
DARK DASHED INDICATES EXISTING FIXTURE OR DEVICE RELOCATED
DARK SOLID INDICATES NEW FIXTURE OR DEVICE
HATCHED ITEMS INDICATES FIXTURE OR DEVICE TO BE REMOVED OR RELOCATED
NOT IN CONTRACT (N.I.C.)
ABV - ABBREVIATION
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AW - ACID WASTE
AWS - ACID WASTE STACK
AVS - ACID VENT STACK
BOP - BOTTOM OF PIPE
BHP - BRAKE HORSE POWER
BTH - BRITISH THERMAL UNIT
CAP - CAPACITY
CD - CONDENSATE DRAIN
COMB - COMBINATION
CONN - CONNECTION
CONT - CONTINUE
CW - COLD WATER
DIA - DIAMETER
DN - DOWN
DWG - DRAWING
ECO - EXTERIOR CLEAN OUT
EFF - EFFICIENCY
ENT - ENTERING
EWC - ELECTRIC WATER COOLER
EWS - EMERGENCY EYEWASH/SHOWER
EWT - ENTERING WATER TEMPERATURE
EXP - EXPANSION
F - FAHRENHEIT
FA - FIRE ALARM
FL - FLOOR
FLA - FULL LOAD AMPS
FLO - FLOOR CLEAN OUT
FD - FLOOR DRAIN
FS - FLOOR SINK
FT - FEET
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GPM - GALLONS PER MINUTE
GW - GREASE WASTE
GWH - GAS WATER HEATER
HB - HOSE BIBB
HP - HORSE POWER
HR - HOUR
HW - HOT WATER
HWR - HOT WATER RETURN
HWS - HOT WATER SUPPLY
IE - INVERT ELEVATION
IN - INCHES
IW - INDIRECT WASTE
KW - KILOWATT
LF - LINEAR FOOT
LWT - LEAVING WATER TEMPERATURE
LIQ - LIQUID
LP - LIQUID PROPANE
MAX - MAXIMUM
MBH - THOUSAND BTU PER HOUR
MCA - MINIMUM CIRCUIT AMPACITY
MECH - MECHANICAL
MEZZ - MEZZANINE
MIN - MINIMUM
MTD - MOUNTED
NC - NORMALLY CLOSED
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
NO - NORMALLY OPEN
NOM - NOMINAL
NTS - NOT TO SCALE
OC - ON CENTER
OW - OILY WASTE
PH - PHASE
POC - POINT OF CONNECTION
PRESS - PRESSURE
PRV - PRESSURE REDUCING VALVE
PSI - POUNDS PER SQUARE INCH
PSIG - PSI GAUGE
PVC - POLYVINYL CHLORIDE PIPE
QTY - QUANTITY
RAD - REFRIGERANT AIR DRYER
RD - ROOF DRAIN
REF - REFRIGERANT
RL - RAIN LEADER
RPM - REVOLUTIONS PER MINUTE
RLA - RATED LOAD AMPS
SH - SHOWER
SOV - SHUT OFF VALVE
SP - STATIC PRESSURE
SRD - SECONDARY ROOF DRAIN
SS - SANITARY SEWER OR STAINLESS STEEL
ST - STORM DRAIN
TEMP - TEMPERATURE
TP - TRAP PRIMER
TYP - TYPICAL
UG - UNDER GROUND
UON - UNLESS OTHERWISE NOTED
V - VENT
VEL - VELOCITY
VLV - VALVE
VSD - VARIABLE SPEED DRIVE
VTR - VENT THRU ROOF
W - WASTE
WCO - WALL CLEAN OUT
WH - WALL HYDRANT
WHA - WATER HAMMER ARRESTER
W/TP - WITH TRAP PRIMER
ALL WORK SHALL BE IN COMPLIANCE WITH THE FOLLOWING CODES, BUT NOT LIMITED TO:
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - BUILDING (FBCB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - EXISTING BUILDING (FBCEB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ACCESSIBILITY (FBCA)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ENERGY CONSERVATION (FBCEC)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - MECHANICAL (FBCM)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - PLUMBING (FBCP)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - FUEL GAS (FBCFG)
8TH EDITION OF THE 2023 FLORIDA FIRE PREVENTION CODE (FFPC)
NFPA 70 - 2020 NATIONAL ELECTRICAL CODE (NEC)
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
A.THE EXTENT OF DEMOLITION WORK SHOWN ON THE DRAWINGS ARE BASED ON EXISTING DRAWINGS AND FIELD
SURVEY AND MAY NOT BE ALL INCLUSIVE. IT IS THE PLUMBING CONTRACTOR'S RESPONSIBILITY TO REMOVE ALL
FIXTURES, PIPING AND OTHER EQUIPMENT AS MAY BE NECESSARY AND AT NO ADDITIONAL COST TO THE OWNER.
B.ALL MEANS OF EGRESS SHALL BE KEPT OPEN AT ALL TIMES.
C.CONTRACTOR SHALL COMPLY WITH APPLICABLE BUILDING CODES FOR ALL DEMOLITION WORK.
D.PROCEED WITH DEMOLITION FROM TOP TO BOTTOM. DO NOT REMOVE ITEMS SUPPORTING OTHER MEMBERS
WITHOUT PROVIDING TEMPORARY OR PERMANENT BRACING AS REQUIRED.
E.EXISTING EQUIPMENT NOT REMOVED BUT DAMAGED DURING THE COURSE OF CONSTRUCTION SHALL BE RESTORED
TO EXISTING CONDITION AT NO ADDITIONAL COST TO THE OWNER.
F.PROTECT ITEMS AND EQUIPMENT ON SITE TO MINIMIZE DAMAGE. ANY DAMAGE INCURRED TO THE SITE SHALL BE
REPAIRED BY THIS CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
G.REMOVAL OF ALL PIPING INCLUDES REMOVAL OF ALL SUPPORTS, HANGERS AND FASTENERS. PENETRATIONS LEFT BY
THE REMOVAL OF PIPING SHALL BE PATCHED TO REMOVE THE APPEARANCE OF DEMOLITION. EXISTING PIPING NOT
SHOWN TO BE REMOVED SHALL BE PROTECTED THROUGHOUT CONSTRUCTION. LEAKS IN PIPING RESULTING FROM
DAMAGE DURING CONSTRUCTION SHALL BE PROMPTLY REPAIRED BY THIS CONTRACTOR.
H.ALL MATERIALS AND EQUIPMENT SHALL BE DISPOSED OF IN ACCORDANCE WITH APPLICABLE LAWS AND
ENVIRONMENTAL REGULATIONS.
I.REFER TO ARCHITECTURAL DRAWINGS FOR FURTHER DEMOLITION REQUIREMENTS. CONTRACTOR TO PROPERLY
REMOVE ALL PLUMBING SYSTEMS WHERE INDICATED AND PROPERLY TERMINATE ALL SYSTEMS.
P-1
EED/SBH
PL
U
M
B
I
N
G
L
E
G
E
N
D
,
N
O
T
E
S
,
S
P
E
C
S
.
&
S
C
H
E
D
U
L
E
S
JMF
DAD
PLUMBING SYMBOLS LEGEND, NOTES, AND SPECIFICATIONS
PLUMBING LEGEND PLUMBING SPECIFICATIONS
SHEET NOTE CALLOUT
ABBREVIATIONS
CODE COMPLIANCE REQUIREMENTS
GENERAL DEMOLITION NOTES
PROVIDE THE FOLLOWING:
SCOPE OF WORK
CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS AS REQUIRED TO PROVIDE A COMPLETE AND OPERATIONAL
PLUMBING SYSTEMS AS INDICATED ON THE DRAWINGS. CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH ALL
OTHER TRADES.
SPECIAL PROVISIONS
ALL WORK SHALL BE IN COMPLIANCE WITH THE 2023 FLORIDA BUILDING CODE (8TH EDITION), 2023 FLORIDA BUILDING
CODE - PLUMBING (8TH EDITION), 2023 FLORIDA ENERGY CONSERVATION CODE (8TH EDITION), ORDINANCES AND
REGULATIONS OF THE LOCAL AUTHORITY HAVING JURISDICTION.
SHOP DRAWINGS
BEFORE PURCHASE OR FABRICATION OF EQUIPMENT AND WITHIN 30 DAYS OF AWARD OF GENERAL CONTRACT,
CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER FOR APPROVAL, 3 COPIES OF SHOP DRAWINGS FOR ALL
EQUIPMENT AND MATERIALS. SHOP DRAWINGS SHALL INDICATE WORKING AND ERECTION DIMENSIONS, ELECTRICAL
CHARACTERISTICS (VOLTS, PHASE AND AMPS), LOCATION AT WHICH MATERIALS AND EQUIPMENT ARE TO BE INSTALLED
AND OTHER ESSENTIAL DATA. PARTIAL OR INCOMPLETE SUBMITTALS WILL NOT BE ACCEPTED. ANY MATERIAL USED
WITHOUT APPROVAL WILL BE REJECTED. PROVIDE SUBMITTALS ON ALL ITEMS EXCEPT PIPING. SUBMIT SHOP DRAWINGS
TO ELECTRICAL CONTRACTOR FOR APPROVAL AND COORDINATION.
MATERIALS
MATERIALS, UNLESS OTHERWISE NOTED, SHALL BE NEW, FREE OF DEFECTS AND IN ACCORD WITH FOLLOWING
SCHEDULES AND PARAGRAPHS. THE APPROVAL OF ANY MATERIALS WILL NOT BE CONSIDERED AS ACCEPTANCE OF WORK
WHERE INSTALLED IF SUCH MATERIALS PROVE DEFECTIVE. WHERE NO SPECIFIC WEIGHTS OR GRADES ARE SPECIFIED,
MATERIALS SHALL BE OF THE GENERALLY ACCEPTED STANDARD WEIGHT AND GRADE.
DRAIN, WASTE AND VENT PIPING
SANITARY PIPING SHALL BE SCHEDULE 40 PVC IN CONFORMANCE WITH ASTM F1488.
WATER SYSTEM (DOMESTIC PIPING)
ABOVE GROUND WATER PIPING SHALL BE TYPE "L" COPPER WITH SWEATED CONNECTIONS. BELOW GROUND PIPING
SHALL BE TYPE "K" COPPER WITH SWEATED CONNECTIONS. PIPING SHALL BE IN CONFORMANCE WITH ASTM B88
A.SOLDER JOINTS WITH FREE FLOWING SOFT LEAD FREE SOLDER (95 5) PER ASTM B32
B.PIPING SHALL BE TESTED HYDROSTATICALLY AT A PRESSURE OF 150 PSIG.
C.AFTER COMPLETION OF WORK, THE PIPING SHALL BE FLUSHED AND STERILIZED IN ACCORDANCE WITH THE FLORIDA
BUILDING CODE.
D.INSULATE ALL HOT WATER PIPING WITH 1 2" ARMAFLEX.
E.THE USE OF PEX PIPING IS NOT APPROVED.
INSTALLATION PIPE SHALL BE CUT ACCURATELY TO MEASUREMENTS ESTABLISHED AT THE JOB SITE AND WORKED INTO
PLACE WITHOUT FORCING, PROPERLY CLEARING ALL WINDOWS, DOORS, AND OTHER OPENINGS. PIPES SHALL HAVE
BURRS REMOVED BY REAMING AND SHALL BE SO INSTALLED AS TO PERMIT FREE EXPANSION AND CONTRACTION
WITHOUT DAMAGE TO JOINTS OR HANGERS.
COMPRESSED AIR
COPPER PIPING AND FITTINGS. OWNER MAY OPT TO USE SCHEDULE 40 PVC PIPE & FITTINGS.
GAS PIPING
SCHEDULE 40 BLACK IRON PIPE & FITTINGS. PAINT PIPING YELLOW AND LABEL.
OPERATION AND MAINTENANCE INSTRUCTION
COMPLETE OPERATING AND MAINTENANCE INSTRUCTIONS MANUALS FOR EACH PIECE OF EQUIPMENT, BOUND IN BOOK
FORM, SHALL BE PREPARED. OPERATING INSTRUCTIONS EXPLAINING PREVENTIVE MAINTENANCE PROCEDURES,
METHODS OF CHECKING THE SYSTEM FOR NORMAL SAFE OPERATION, AND PROCEDURE FOR SAFELY STARTING AND
STOPPING THE SYSTEM SHALL BE PREPARED AND INCLUDED WITH THE MANUALS.
GUARANTEE AND WARRANTIES
A.FURNISH OWNER WITH A WRITTEN GUARANTEE PROTECTING THE OWNER FROM COSTS DUE TO POOR WORKMANSHIP
AND FAULTY MATERIALS OR EQUIPMENT FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE.
B.FURNISH OWNER WITH ORIGINAL EQUIPMENT FACTORY WARRANTIES.
TEST PIPING AT PRESSURE LISTED BELOW:
A.HYDROSTATIC PRESSURE TEST:
a.SANITARY AND ROOF DRAINAGE PIPING: TESTED UNDER THE REQUIREMENTS OF THE FBCP, BUT NOT LESS THAN
EQUIVALENT TO 10 FEET OF WATER.
b.WATER PIPING: 1-1/2 TIMES THE OPERATING PRESSURE, BUT NOT LESS THAN 100 PSIG AT THE TOP MOST OUTLET.
DISINFECTION OF DOMESTIC WATER PIPING SYSTEM
A.DISINFECTION SHALL BE PERFORMED AT EACH INDIVIDUAL BUILDING.
B.ALL LEAD TESTING TO BE PERFORMED IN ACCORDANCE WITH EPA AND THE LOCAL COUNTY HEALTH DEPARTMENT
STANDARDS AND REGULATIONS AND MEET OR EXCEED THEIR ALLOWABLE SAFE DRINKING WATER PARAMETERS.
C.PRIOR TO STARTING WORK, VERIFY SYSTEM IS COMPLETE, FLUSHED AND CLEAN.
D.ENSURE PH OF WATER TO BE TREATED IS CORRECT.
E.INJECT DISINFECTANT, FREE CHLORINE IN LIQUID, POWDER, TABLET OR GAS FORM, THROUGHOUT SYSTEM TO OBTAIN
50 TO 80 MG/L RESIDUAL.
F.MAINTAIN DISINFECTANT IN SYSTEM FOR 24 HOURS.
G.IF FINAL DISINFECTANT RESIDUAL TESTS LESS THAN 25 MG/L, REPEAT TREATMENT.
H.FLUSH DISINFECTANT FROM SYSTEM UNTIL RESIDUAL IS EQUAL TO THAT OF INCOMING WATER OR 1.0 MG/L.
I.BLEED WATER FROM OUTLETS TO ENSURE DISTRIBUTION AND TEST FOR CONTAMINANTS AND LEAD CONTENT AT ALL
THE REMOTE LOCATIONS AND AT SEVERAL INTERMEDIATE LOCATIONS. TEST LOCATIONS SHALL BE AT THE SERVICE
ENTRY TO THE PROPERTY LINE, THE WATER ENTRY AT EACH BUILDING AND AT THE MOST REMOTE LOCATIONS OF THE
CONSTRUCTED DOMESTIC WATER PIPING SYSTEM.
J.TAKE WATER SAMPLE NO SOONER THAN 48 HOURS AFTER FLUSHING AT EACH BUILDING AND ANALYZE IN
ACCORDANCE WITH AWWA C651.
K.ALL WATER SAMPLES FOR LEAD SAMPLING SHALL BE 250 ML IN VOLUME. SAMPLING BOTTLES SHALL BE OBTAINED
FROM THE CONTRACTOR'S CERTIFIED DRINKING WATER LABORATORY.
L.TESTING OF THE WATER SAMPLES SHALL BE PERFORMED BY THE CONTRACTOR'S CERTIFIED DRINKING WATER
LABORATORY IN COORDINATION WITH THE COUNTIES RISK MANAGEMENT DEPARTMENT.
M.OWNER'S REPRESENTATIVE TO WITNESS ALL TEST.
*ANY CHANGES TO THESE DOCUMENTS BASED ON CONTRACTOR REQUESTED REVISIONS SHALL BE CONSIDERED
ADDITIONAL SERVICES.
#
POINT OF CONNECTION
POINT OF DISCONNECT
MISCELLANEOUS
CONTROL VALVE
HOT WATER PIPING
HI-TEMP HOT WATER PIPING
CONDENSATE
CONNECTION, BOTTOM
CONNECTION, TOP
HW
140°
CHECK VALVE
STRAINER
BUTTERFLY VALVE
CALIBRATING BALANCING VALVE
MIXING VALVE
UNION
VENT PIPING
CW COLD WATER PIPING
SANITARY WASTE PIPINGSS
STORM DRAIN
(TEMPERED) HOT WATER RECIRCULATION PIPINGHWR
EWH-EQUIPMENT TAG
GENERAL NOTES
1.ALL WORK AND MATERIALS SHALL BE PROVIDED AND INSTALLED IN COMPLIANCE WITH THE FLORIDA BUILDING
CODES AND AS PER MANUFACTURERS INSTRUCTION.
2.PROVIDE SHUT-OFF VALVES FOR BOTH HOT AND COLD DOMESTIC WATER PIPING FEEDING GROUPS OF FIXTURES,
AND AS PER FBC-P 606.1.
3.PROVIDE ALL EXTERIOR WALL HYDRANTS/BIBBS WITH SHUT-OFF BALL VALVES IMMEDIATELY INSIDE ABOVE THE
CEILING OR OTHER ACCESSIBLE LOCATION.
4.PRIME AND PAINT ALL OUTSIDE PIPE AND PIPE SUPPORTS IF THEY ARE NOT GALVANIZED.
5.INSTALL WATER HAMMER ARRESTORS WHERE DIRECTED BY CODE.
6.PROVIDE CLEANOUTS AS DIRECTED BY FBC-P.
7.PROVIDE CLEANOUTS AT THE BASE OF ALL SEWER RISERS ON EACH FLOOR.
8.EXACT LOCATIONS AND MOUNTING HEIGHTS OF PLUMBING FIXTURES SHALL BE OBTAINED FROM THE
ARCHITECTURAL DRAWINGS.
9.FLOOR CLEAN OUTS SHALL BE INSTALLED FLUSH TO FINISHED FLOOR. INSTALL FLOOR CLEAN OUTS (FCO) AS CLOSE
TO HIGH POINT AS POSSIBLE. NO DISHING PERMITTED.
10.ALL PLUMBING FIXTURE VENTS SHALL TERMINATE A MINIMUM OF 12" FROM ANY VERTICAL SURFACE AND 10' FROM
ANY OUTSIDE AIR INTAKES.
11.ALL PLUMBING WORK SHALL BE INSTALLED TO AVOID INTERFERENCE WITH ELECTRICAL AND MECHANICAL
EQUIPMENT AND STRUCTURAL FRAMING. INSTALL EQUIPMENT SUCH THAT REMOVAL DOES NOT REQUIRE REMOVAL
OF CONNECTED PIPING.
12.BEFORE COMMENCEMENT OF WORK, CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS, ELEVATIONS AND
CHARACTERISTICS OF ALL UTILITIES AND PIPING, AND SHALL NOTIFY THE ARCHITECT/ENGINEER OF ANY
DISCREPANCIES.
13.ALL WASTE AND VENT PIPING SHALL SLOPE AT 1/8" PER FOOT UNLESS INDICATED OTHERWISE.
14.INSULATE ALL EXPOSED PVC LOCATED IN RETURN AIR PLENUM SPACES WITH APPROVED FIRE WRAP INSULATION.
15.AVOID THE USE OF PLASTICS IN RETURN AIR PLENUMS.
16.ALL WASTE PIPING SHOWN ON THESE DRAWINGS IS LOCATED BELOW FLOOR SLAB (UNLESS NOTED OTHERWISE). ALL
DOMESTIC WATER AND VENT PIPING IS LOCATED ABOVE THE CEILING (UNLESS NOTED OTHERWISE).
GREASE WASTE PIPING
COMPRESSED AIR PIPING
GAS PIPING
CD
SD
V
GW
A
G
GATE VALVE OR BALL VALVE
ECO/FCO EXTERIOR CLEAN OUT AND FLOOR CLEAN OUT
WALL CLEANOUTWCO
FLOOR DRAIN
FLOOR SINK
FD-
FS-
NOTESMODEL
MANUFACTURE /
WASTEHW
PIPE SIZE
CWACCESSORIES
DESCRIPTION /EQUIPMENT
PLUMBING FIXTURE SCHEDULE
VENT
SK-1
SINK
SINGLE
STAINLESS STEEL
(18 GA.)
WITH GOOSENECK FAUCET
1/2"1/2"2"1-1/2"
ELKAY
LUSTERTONE
SEE
BELOW
NOTES:
TAG
1.PROVIDE SHUT OFF VALVES AND P-TRAPS AT ALL PLUMBING FIXTURES.
2.PROVIDE HANDICAP FIXTURES IN ALL HANDICAP DESIGNATED
RESTROOMS.
3.ROUTE 5 8" DRAIN, 3 8" HW TO ALL DISHWASHERS FROM NEAREST SINK.
4.PROVIDE PRESSURE BALANCING VALVE AND ANTI-SCALD DEVICE FOR ALL
SHOWERS AND TUBS.
5.COORDINATE SINK SIZE WITH CABINET INSTALLER.
6.PROVIDE ULTRA-COMPACT THERMOSTATIC MIXING VALVE, WITH
TEMPERATURE GAUGE, FOR ALL LAVATORIES AND HAND SINKS, AS
MANUFACTURED BY WEBSTONE.
7.CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL DRAWINGS FOR
ALL FLOOR AND WALL MOUNTED FIXTURES. PROVIDED CARRIERS AS
REQUIRED.
8.CONTRACTOR TO PROVIDE A SEPARATE COST FOR ALL PLUMBING
FIXTURES IN BID PACKAGE. OWNER TO MAKE FINAL SELECTION OF
FIXTURES. (CONTRACTOR TO COORDINATE WITH OWNER).
WATER HAMMER ARRESTOR
HANGERS / SUPPORTS
PUMPS / CONTROLS
INSULATION
ALL FIXTURES
ALL PLUMBING EQUIPMENT
ITEM COPY FOR
OWNER
PRODUCT DATA SHOP
DRAWINGS
TEST
REPORTS
COORDINATION
DRAWINGS
WIRING
DIAGRAMS
O & M
MANUAL
1 2 3 4 1 2 1 2 1 2 1 2 1 2
NOTES:
1- FOR REVIEW
2- FOR RECORD
3- COLOR SELECTION
4- SAMPLE
NOTE:
FOR ALL MATERIALS FOR CONSTRUCTION, INSTALLATION REQUIREMENTS AND
TESTING REQUIREMENTS, REFER TO CONTRACT SPECIFICATIONS.
CONTRACTOR SHALL SUBMIT ALL ITEMS UNDER ONE SUBMITTAL THAT REFERENCES
DDC PROJECT NUMBER. NO PARTIAL SUBMITTALS WILL BE ACCEPTED. ALL
SUBMITTALS SHALL BE EMAILED TO INFO@DDC-ENGINEERS.COM .
REVIEW
WATER HEATER
PIPING / FITTINGS
SHOP DRAWING SUBMITTALS
N.T.S.
FLOOR CLEANOUT DETAIL
P-D006
FLOW
PLUG IF END
OF LINE
CLEANOUT PLUG AND
BODY. SEE SPECS.
ADJUSTING COLLAR
RISER
1
8 BEND FULL
SIZE, 4" MAX.
COVER
FIN. FLOOR
P4
N.T.S.
DETAIL
P-D006
FLOW
PLUG IF END
OF LINE
CLEANOUT PLUG AND
BODY. SEE SPECS.
ADJUSTING COLLAR
RISER
1
8 BEND FULL
SIZE, 4" MAX.
CONCRETE BASE
SEWER LINE
EXTERIOR CLEANOUT
2"-0"
COVER
EARTH
6"
P3
FOR WALL CONST.
SEE ARCH. DWGS.
PLUG
SCREW
COUNTERSUNK
CLEANOUT
ACCESS COVER
POLISHED S.S.
LENGTH TO SUIT
1/8 BEND AT END
WASTE LINE w/
OR VENT
AS WASTE
CLEANOUT
MAY EXTEND
TEE
WASTE LINE
OF LINE CLEANOUT
WALL CLEANOUT DETAIL
N.T.S.
P
P2
N.T.S.
INSULATED
PIPE HANGER DETAIL
M-D009
SIZES UP TO 3"
SINGLE
MULTIPLE
PIPE
PIPE SADDLE
(TYP.)
ALL INSULATION PASSES
THRU HANGER UNBROKEN LOCKNUT (TYP.)
UNISTRUT OR
ANGLE IRON
WASHER (TYP.)
PIPE SADDLE
(18 GA., 18" LONG)
ATTACH TO
STRUCTURE
CONTINUOUS
THREADED ROD
U-BOLT
PIPE INSULATION
PIPE
P1
2
A
A
A.8
A.8 B.8
A.8
3
4
5
6
MGMT.
OFFICE #1
107
MGMT.
OFFICE #2
108
CONF. RM.
109
RECEPT.
AREA
110
TRAINING #1
112
CORR.
111
TRAINING #2
113
TRAINING #3
114
TRAINING #4
115
FOYER
117CORR.
118
UTIL.
RM.
119
R.R.
120
R.R.
121
PILOT
BRIEFING RM.
123
CORR.
122
RECEPT.
OFFICE
116
2" SS
ECO
SK-1
2" SS
1 2" CW/HW W1
P-2
1
S1
P-2
11
D
D C B
A
A
10
9
C.2A.9
SIMULATOR
AREA
100
OFFICE
#1
101
OFFICE
#2
102
BREAKROOM
103
UTILITY
ROOM
104
R.R.
105
R.R.
106
SK-1
1 1 2" SS/
1 2" CW/HW
TO SK-1
S2
P-2
1
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
P-2
EED/SBH
PL
U
M
B
I
N
G
S
E
W
E
R
P
L
A
N
JMF
DAD
#GENERAL NOTES
1.PROVIDE WATER HAMMER ARRESTORS FOR ALL PLUMBING FIXTURES.
2.CONTRACTOR TO CONFIRM PIPE SIZES, LOCATIONS AND FLOW.
3.PROVIDE SHUT OFF VALVES FOR EACH FIXTURE.
4.PROPERLY ANCHOR ALL PIPING TO STRUCTURE.
5.INSULATE ALL HOT WATER PIPES WITH 1" ARMAFLEX.
6.CONTRACTOR TO SAW CUT WALLS AND SLAB AS NECESSARY TO INSTALL NEW WORK.
PROPERLY PATCH AND REPAIR.
NORTH BAY 3/16" = 1'-0"
PLUMBING PLAN
S1
P-2
N.T.S.
SEWER RISER DIAGRAM
1 2" CW/HW
S2
P-2
N.T.S.
SEWER RISER DIAGRAM
1 1 2" SS
S
K
-
1
11 4"
SK-1
11 4" VENT, CONNECT
TO EXISTING
2" SS
2" SS
ECO
1 2" CW/HW
FROM EX. EWH
WATER HAMMER ARRESTORS (TYP.)
S
K
-
1
W1
P-2 N.T.S.
WATER RISER DIAGRAM
#PLAN NOTES
1.ROUTE 1/2" CW/HW TO SK-1 FROM NEAREST WATER HEADER.
SOUTH BAY 3/16" = 1'-0"
PLUMBING PLAN
PP POWER POLE LOCATION - DATA & J-BOX LOCATE ABOVE CEILING. PROVIDE 10' ADDITIONAL
WIRE FOR FIELD ADJUSTMENTS
2'x2' SURFACE MOUNTED FIXTURE
2'x4' RECESSED FIXTURE
2'x4' SURFACE MOUNTED FIXTURE
1'x4' RECESSED FIXTURE
4' WALL MOUNTED FIXTURE
4' FIXTURE
4' SUSPENDED FIXTURE
4' WALL MOUNTED FIXTURE
WALL WASH LIGHT FIXTURE
RECESSED DOWNLIGHT
SURFACE MOUNTED DOWNLIGHT
SUSPENDED PENDANT LIGHT FIXTURE
DECORATIVE PENDANT FIXTURE
HIGH BAY LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
EXTERIOR FLOOD LIGHT FIXTURE
8' FIXTURE
8' WALL MOUNTED FIXTURE
POLE MOUNTED PARKING LOT LUMINARE
CEILING MOUNTED TRACK LIGHTING
CEILING MOUNTED EXIT SIGN WITH BATTERY BACKUP - SINGLE FACE - ARROW INDICATES DIRECTION
WALL MOUNTED EXIT SIGN WITH BATTERY BACKUP - SINGLE FACE - ARROW INDICATES DIRECTION
CEILING MOUNTED EXIT SIGN WITH BATTERY BACKUP - DOUBLE FACE - ARROW INDICATES DIRECTION
EMERGENCY LIGHT WITH BATTERY BACKUP - DUAL HEAD
COMBINATION EXIT / EMERGENCY LIGHT WITH BATTERY BACKUP
(4) 4-WAY
(2) DOUBLE POLE
(D) DIMMER
(DF) WALL BOX DIMMER
(F) FAN RATED SWITCH
(K) KEYED SWITCH
CEILING MOUNTED OCCUPANCY SENSOR
FIXTURES WITH DIAGONAL SHADING DENOTES EMERGENCY FIXTURE WITH INTEGRAL
1400 LUMEN BATTERY PACK OR BACKUP INVERTER. (NL INDICATES NIGHT LIGHT)
DUPLEX GFI RECEPTACLE
DUPLEX GFI RECEPTACLE MOUNTED ABOVE COUNTER
QUAD RECEPTACLE
QUAD RECEPTACLE MOUNTED ABOVE COUNTER
QUAD GFI RECEPTACLE
DUPLEX RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX (WIREMOLD EVOLUTION SERIES OR EQUAL)
DUPLEX GFI RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX, WITH GASKETED COVER
DUPLEX RECEPTACLE - FLUSH MOUNTED IN CEILING
DUPLEX GFI RECEPTACLE - FLUSH MOUNTED IN CEILING
QUAD RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX (WIREMOLD EVELUTION SERIES OR EQUAL)
QUAD GFI RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX, WITH GASKETED COVER
QUAD RECEPTACLE - FLUSH MOUNTED IN CEILING
QUAD GFI RECEPTACLE - FLUSH MOUNTED IN CEILING, WITH GASKETED COVER
SPECIAL PURPOSE OUTLET
SPECIAL PURPOSE OUTLET MOUNTED ABOVE COUNTER
SPECIAL PURPOSE OUTLET
PLUG IN STRIP WITH RECEPTACLES 18" O.C. UNLESS NOTED OTHERWISE
J-BOX
J-BOX - FLUSH MOUNTED IN FLOOR
FAN RATED J-BOX - FLUSH MOUNTED WITHIN CEILING
EXHAUST FAN MOTOR
COMBINATION EXHAUST FAN/LIGHT
HOME RUN
MOTOR OPERATED CEILING PADDLE FAN. PROVIDE CONNECTION BOX FOR WEIGHT OF FAN PLUS
EF
EXISTING COMM AND/OR DATA OUTLET
EXISTING COMM AND/OR DATA OUTLET
NEW COMM/DATA OUTLET WITH FLUSH MOUNTED 4" SQUARE SINGLE GANGE JUNCTION BOX 18"AFF
UNLESS NOTED OTHERWISE. EXTEND 1" CONCEALED CONDUIT TO ABOVE ACCESSIBLE CEILING AND
STUB-OUT WITH PLASTIC BUSHING OR AS NOTED. INSTALL PULL WIRE.
NEW COMM/DATA OUTLET WITH FLUSH MOUNTED 4" SQUARE SINGLE GANGE JUNCTION BOX MOUNTED
ABOVE COUNTER UNLESS NOTED OTHERWISE. EXTEND 1" CONCEALED CONDUIT TO ABOVE ACCESSIBLE
CEILING AND STUB-OUT WITH PLASTIC BUSHING OR AS NOTED. INSTALL PULL WIRE.
NEW COMM/DATA OUTLET JUNCTION BOX FLUSH MOUNTED WITHIN FLOOR. EXTEND 1" CONCEALED
CONDUIT TO ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING OR AS NOTED.
INSTALL PULL WIRE.
NEW COMM/DATA OUTLET JUNCTION BOX FLUSH MOUNTED IN CEILING. EXTEND 1" CONCEALED
CONDUIT TO ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING OR AS NOTED.
REVISION REFERENCE #
#WIRE CALLOUT
TRANSFORMER
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED
INDICATES LIGHTING FIXTURE TYPE
INDICATES SWITCH DESIGNATION
INDICATES CIRCUIT NUMBER
a
A
14
LIGHT DASHED INDICATES EXISTING FIXTURE OR DEVICE
DARK DASHED INDICATES EXISTING FIXTURE OR DEVICE RELOCATED
DARK SOLID INDICATES NEW FIXTURE OR DEVICE
HATCHED ITEMS INDICATES FIXTURE OR DEVICE TO BE REMOVED OR RELOCATED
SYSTEM. PROVIDE PLUG LOAD CONTROLLABLE RECEPTACLES WITH PERMANENT MARKINGS PER
NEC 406.3(E) AND "CONTROLLED".
NOT IN CONTRACT (N.I.C.)
KCMIL THOUSAND OF CIRCULAR MILS
KVA KILOVOLT-AMPERES
KW KILOWATT
LTG LIGHTING
MCM THOUSANDS OF CIRCULAR MILS
MCB MAIN CIRCUIT BREAKER
MCP MOTOR CIRCUIT PROTECTION
MCU MASTER OR MOTOR CONTROL UNIT
MH METAL HALIDE
MLO MAIN LUG ONLY
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASS.
NF NON-FUSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
O.C.ON CENTER
P POLE
PNL PANELBOARD
PVC POLYVINYL CHLORIDE
RGS RIGID GALVANIZED STEEL
RM ROOM
RTU ROOF TOP UNIT
SPEC SPECIFICATION
SS SUPER SAVER OR STAINLESS STEEL
TBB TELEPHONE/COMPUTER TERMINAL BOARD
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLTS
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W WIRE
WP WEATHERPROOF
A AMPERES
AC ALTERNATING CURRENT OR AIR CONDITIONER
ADA AMERICANS W/ DISABILITIES ACT
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPS INTERRUPTING CAPACITY
AWG AMERICAN WIRE GAUGE
C CONDUIT
CATV CABLE TELEVISION
CH COUNTER HEIGHT
COND CONDUIT
CU COPPER OR CONDENSER UNIT
DISC DISCONNECT
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
ELEC ELECTRICAL
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING
EXIST EXISTING
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
G GROUND
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HVAC HEATING, VENTILATING AND AIR CONDITIONING
J JUNCTION
KAIC (THOUSAND) AMPERE INTERRUPTING CAPACITY
LED COVE LIGHT FIXTURE
LIGHTING SEQUENCE OF OPERATION CALLOUT
#RISER EQUIPMENT NOTES
POWER TO MODULAR FURNITURE. COORDINATE ALL REQUIREMENTS WITH FURNITURE SUPPLIER
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER WITH BOTTOM HALF CONTROLLED BY OCCUPANCY
SENSOR/LIGHTING CONTROL SYSTEM. PROVIDE PLUG LOAD CONTROLLABLE RECEPTACLES WITH
PERMANENT MARKINGS PER NEC 406.3(E) AND "CONTROLLED".
J-BOX - WALL MOUNTED
1.ALL ELECTRICAL CONDUITS SHALL CARRY A SEPARATE GREEN INSULATED COPPER WIRE SIZED PER NEC UNLESS
OTHERWISE INDICATED IN THE DRAWINGS.
2.COORDINATE ELECTRICAL REQUIREMENTS FOR ALL EQUIPMENT TO BE INSTALLED BY OTHER TRADES.
3.MULTIWIRE BRANCH CIRCUITS IN A SINGLE CONDUIT RUN SHALL BE ALLOWED. WIRE SIZES MIGHT REQUIRE UPSIZING
FOR CONDUITS CONTAINING MORE THAN 3 CURRENT CARRYING CONDUCTORS, AS REQUIRED BY THE DERATING
GUIDELINES OF ARTICLE 310.15 IN THE 2020 NEC.
4.BRANCH CIRCUIT FEEDER WIRE AND CONDUIT SIZES ARE INDICATED ON PANEL SCHEDULES.
5.RESTROOM EXHAUST FANS SHALL BE CONTROLLED BY RESTROOM LIGHT SWITCH.
6.REFER TO MECHANICAL PLANS FOR EXACT LOCATIONS AND REQUIREMENTS OF MECHANICAL EQUIPMENT.
7.EMERGENCY LIGHTING AND EXIT LIGHTING CONNECTED AHEAD OF LOCAL SWITCH.
8.FIRE ALARM DESIGN BY OTHERS. CONTRACTOR SHALL PROVIDE AND SUBMIT FULL SET OF FIRE ALARM DRAWINGS,
DESIGNED, SIGNED AND SEALED BY A FLORIDA LICENSED ENGINEER.
9.COORDINATE SIGN LIGHT LOCATION WITH OWNER/ARCHITECT.
10.EXTERIOR LIGHTING AND SIGN LIGHTING SHALL BE CONTROLLED BY ASTRONOMICAL TIME CLOCK.
11.CONTRACTOR SHALL ENGAGE THE ENGINEER TO INSPECT COMPONENTS AND FUNCTION OF LIGHTING CONTROL
SYSTEM INSTALLED, AS PER THE 8TH EDITION OF THE FLORIDA BUILDING CODE ENERGY CONSERVATION SECTION
C405 AND C408.3.1. ADDITIONAL ENGINEERING FEES MAY APPLY.
12.WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL
BE PROVIDED TO THE BUILDING OWNER AND CODE OFFICIAL, INCLUDING A SINGLE LINE DIAGRAM OF THE BUILDING'S
ELECTRICAL DISTRIBUTION, AS REQUIRED PER THE 8TH EDITION OF THE FLORIDA BUILDING CODE - ENERGY
CONSERVATION C408.3.2.
13.ALL LIGHTING SHALL BE CONTROLLED BY OCCUPANCY SENSORS, AS MANUFACTURED BY WATT STOPPER OR EQUAL,
UNLESS NOTED OTHERWISE. RESTROOMS EXHAUST FANS SHALL BE CONNECTED TO LIGHTING CIRCUIT AND CONTROL
SWITCH UNLESS NOTED OTHERWISE. OCCUPANCY SENSORS TO BE DUAL TECHNOLOGY UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL CONSULT REPRESENTATIVE FOR TYPE AND PLACEMENT OF OCCUPANCY SENSORS AND PROVIDE
SHOP DRAWINGS.
14.THIS PROJECT IS IN COMPLIANCE WITH 8TH EDITION FBC-EC C405.5.3 & NEC 210.19 WITH REGARDS TO VOLTAGE DROP
FOR BOTH DISTRIBUTION PANEL & DOWNSTREAM BRANCH CIRCUITS.
15.AFTER WALLS ARE FRAMED, MARK ALL OUTLET, DATA, SWITCH, ETC. LOCATIONS ON THE GROUND AND CONFIRM
LOCATION AND MOUNTING HEIGHTS WITH OWNER PRIOR TO ANY CONDUIT, ETC. IS INSTALLED.
16.PROVIDE TAMPER - RESISTANT RECEPTACLES AS REQUIRED PER NEC 406.12
17.SURGE PROTECTION DEVICES (SPD) SHALL BY PQ PROTECTION OR EQUAL. BRANCH PANELS: PQC160, DISTRIBUTION
PANELS: PQC320, SERVICES 2500A AND LARGER: PQS300, SERVICES 3000A AND LARGER: PQS400. CONTRACTOR SHALL
COORDINATE VOLTAGE REQUIRED FOR SURGE PROTECTION DEVICE(S). WHERE PANEL IS RECESSED, SPD SHALL BE
RECESSED. INSTALL SPD PER MANUFACTURERS RECOMMENDATION.
FLUSH MOUNTED TV OUTLET (WIREMOLD EVOLUTION EFS SERIES OR EQUAL) WITH RECEPTACLE, TV
CONNECTION, AND DATA CONNECTION. EXTEND 1.5" CONCEALED CONDUIT, FOR TV AND DATA CABLE,
TO ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING OR AS NOTED. INSTALL PULL
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
(M) MOTOR RATED SWITCH - 1 OR 2 POLE 30 AMP WITH INTEGRAL THERMAL OVERLOADS
(OC) WALL MOUNTED OCCUPANCY SENSOR SWITCH
FIXTURES WITH DIAGONAL LINE DENOTES NIGHT LIGHT FIXTURE (NL INDICATES NIGHT LIGHT)
A.THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY
THIS WORK BEFORE SUBMITTING PROPOSAL SO AS TO BECOME FAMILIAR WITH EXISTING WORK. SUBMISSION OF A
PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR
LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE BY DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.
IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD
LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN EQUIPMENT ROUTING AS
DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE NECESSARY AND IT IS
INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD
THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL
EXISTING CONDITIONS, PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
B.ALL DEVICES AND EQUIPMENT NOT SHOWN AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS
OTHERWISE NOTED. INSTALL AS REQUIRED TO MAINTAIN CONTINUITY TO EXISTING DEVICES AND EQUIPMENT THAT
ARE TO REMAIN.
C.ALL EQUIPMENT AND MATERIAL REMOVED AND NOT REUSED SHALL BE TURNED OVER TO THE OWNER OR AT THE
OWNERS REQUEST LEGALLY DISPOSED OF BY THE CONTRACTOR.
D.ALL ELECTRICAL DEVICES THAT ARE REMOVED SHALL BE REMOVED AS DIRECTED BY THE OWNER, AND CEILING OR
WALL SHALL BE PATCHED TO MATCH EXISTING OR NEW FINISH. ALL PATCHES OR CEILING PLATES SHALL BE PATCHED
OR PAINTED AS DIRECTED BY ARCHITECTURAL DRAWINGS.
E.ALL EXISTING ELECTRICAL EQUIPMENT IS NOT SHOWN. IT IS THE CONTRACTORS RESPONSIBILITY TO BECOME
FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND INCLUDE IN HIS BID THE REMOVAL OF ALL EQUIPMENT,
CONDUIT, WIRE, ETC. THAT IS NOT BEING REUSED BACK TO ITS SOURCE.
F.ALL CONCRETE, WALL PATCHING, CEILING REPAIR, AND OTHER GENERAL WORK REQUIRED FOR INSTALLING THE
ELECTRICAL SYSTEMS AND TO REPAIR TO "LIKE NEW CONDITION" TO BE PROVIDED AND INSTALLED BY THE
CONTRACTOR.
G.PROVIDE AND INSTALL ANY ADDITIONAL HANGERS/SUPPORTS REQUIRED TO ACCOMMODATE ANY EQUIPMENT
RELOCATIONS.
H.COORDINATE ALL CEILING MOUNTED DEVICES WITH ARCHITECTURAL REFLECTED CEILING AND WORK OF ALL OTHER
TRACES.
I.FOR NEW ELECTRICAL DEVICES WITHIN EXISTING WALL PARTITIONS, CONTRACTOR SHALL BE PERMITTED TO USE
METAL CLAD CABLE. PROVIDE SUBMITTAL PRIOR TO ROUGH-IN.
J.ITEMS NOTED AS EXISTING TO BE REMOVED SHALL BE REMOVED COMPLETE. REMOVAL SHALL INCLUDE CONDUIT
AND WIRE BACK TO BRANCH PANEL.
K.FOR ALL PANELS AFFECTED BY RENOVATION, CONTRACTOR SHALL TRACK ALL EXISTING CIRCUITS AND REMOVE
WIRING AND CONDUIT BACK TO PANEL FOR CIRCUITS NO LONGER IN USE. PROVIDE NEW TYPED PANEL DIRECTORY
AND RELABEL ALL UNUSED CIRCUIT BREAKERS AS SPARE.
L.THE WORK SHALL INCLUDE REVISIONS, DEMOLITION, MODIFICATIONS AND REWORK OF THE EXISTING FACILITY AND
SYSTEMS AS REQUIRED FOR INSTALLATION OF NEW WORK, AND FOR CONNECTIONS BETWEEN EXISTING WORK AND
NEW WORK WHERE REQUIRED. THE WORK SHALL ALSO INCLUDE THE COMPLETION OF ELECTRICAL POWER AND
CONTROL CIRCUITS, FOR DEVICES AND EQUIPMENT THAT ARE TO REMAIN IN SERVICE, IF THE CIRCUITS ARE BROKEN
BY DEMOLITION WORK, OR BY THE REMOVAL OR CUTTING OF EXISTING BUILDING CONSTRUCTION, EXISTING DEVICES
OR EQUIPMENT. EXISTING CONDUIT WIRING SHALL BE REROUTED AND CONNECTED WHERE NECESSARY.
E-1
EED
EL
E
C
T
R
I
C
A
L
L
E
G
E
N
D
,
N
O
T
E
S
,
&
S
P
E
C
I
F
I
C
A
T
I
O
N
S
JMF
DAD
ELECTRICAL SYMBOLS LEGEND, NOTES, AND SPECIFICATIONS
LIGHTING
2'x2' RECESSED FIXTURE
POWER(SEE LIGHTING FIXTURE SCHEDULE)
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
ELECTRICAL SPECIFICATIONS
SWITCHES
SINGLE POLE SWITCH - TOGGLE TYPE - MOUNT 48" AFF
SUBSCRIPT INDICATES AS FOLLOWS:
(a) FIXTURES CONTROLLED BY SWITCH
(3) 3-WAY
ELECTRICAL SERVICE SHUNT TRIP BREAK GLASS STATION
ADDITIONAL 200 LBX. (BASIS OF DESIGN, INTERIOR: OCEANA OUTDOOR W LED LIGHT 52" FAN 100W;
EXISTING COMM AND/OR DATA OUTLET 18"AFF
EXISTING COMM AND/OR DATA OUTLET MOUNTED ABOVE COUNTER
NL
DATA/COMMUNICATION
WALL MOUNTED OCCUPANCY SENSOR
INSTALL PULL WIRE.
SHEET NOTE CALLOUT
SERVICE AND DISTRIBUTION
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION MOTOR STARTER/FUSED DISCONNECT SWITCH
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, RECESSED MOUNTED
SURGE PROTECTION DEVICE (SPD)
METER
MISCELLANEOUS
TIME CLOCK
PHOTOCELL SENSOR
CARD READER. DESIGN BY OTHERS. CONTRACTOR SHALL COORDINATE.
SPEAKER. DESIGN BY OTHERS. CONTRACTOR SHALL COORDINATE.
ABBREVIATIONS
PHONE/DATA TO MODULAR FURNITURE. COORDINATE ALL REQUIREMENTS WITH FURNITURE SUPPLIER.
SHOP DRAWING SUBMITTALS
WIRE. COORDINATE MOUNTING HEIGHTS WITH OWNER PRIOR TO INSTALLATION.
GENERAL DEMOLITION NOTES
1'x4' SURFACE MOUNTED FIXTURE
1'x4' SUSPENDED FIXTURE
QUAD GFI RECEPTACLE MOUNTED ABOVE COUNTER
DUPLEX RECEPTACLE WITH BOTTOM HALF CONTROLLED BY OCCUPANCY SENSOR/LIGHTING CONTROL
GENERAL
1.ALL WORK SHALL BE IN ACCORDANCE WITH THE 2020 NATIONAL ELECTRICAL CODE (N.E.C.), 2023 FLORIDA ENERGY
CONSERVATION CODE (8TH EDITION), ALL LOCAL CODES, ORDINANCES, REGULATIONS AND UTILITY POWER AND
TELEPHONE COMPANY STANDARDS.
2.ALL WIRE SHALL BE COPPER TYPE "THHN" FOR SIZES UP TO #8 AND TYPE "THW FOR #6 AND LARGER (UNLESS
OTHERWISE NOTED). MINIMUM WIRE SIZE SHALL BE #12 AWG.
3.ALL BRANCH AND FEEDER CIRCUITS SHALL CONTAIN A SEPARATE GROUNDING CONDUCTOR AND SHALL BE SIZED AND
BONDED IN ACCORDANCE WITH ARTICLE 250 OF THE N.E.C.
4.ALL CONDUIT INSTALLED IN INTERIOR LOCATIONS SHALL BE TYP E.M.T. WITH COMPRESSION FITTING CONNECTORS AND
COUPLINGS. ALL CONDUIT INSTALLED IN EXTERIOR LOCATIONS, ABOVE GRADE, SHALL BE GALVANIZED RIGID CONDUIT.
ALL CONDUIT BELOW GRADE SHALL BE SCHEDULE 40 PVC. ALL CONDUITS SHALL BE CONCEALED. THE USE OF MC
CABLE IS ACCEPTABLE.
5.CONTRACTOR TO COORDINATE THE LOCATION OF RECEPTACLES, CONTROL CIRCUITS, COMMUNICATIONS AND DATA
OUTLETS, LIGHTING FIXTURES AND DEVICES WITH THE OWNER'S REPRESENTATIVE PRIOR TO INSTALLATION.
6.DRAWINGS ARE DIAGRAMMATIC - CONTRACTOR SHALL REFER TO ARCHITECTURAL, CIVIL AND STRUCTURAL DRAWINGS
AND FIELD CONDITIONS FOR ALL DIMENSIONS.
7.CONTRACTOR SHALL OBTAIN AND FURNISH ALL PERMITS REQUIRED. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT,
APPLIANCES AND TOOLS TO PERFORM ALL WORK NECESSARY FOR THE COMPLETE EXECUTION OF THE ELECTRICAL
WORK AS SHOWN ON THE DRAWINGS. PROVIDE WORK NOT SPECIFICALLY SHOWN OR SPECIFIED, YET REQUIRED TO
INSURE PROPER AND COMPLETE OPERATION OF ALL SYSTEMS AND TO SATISFY THE DESIGN INTENT IN THE WORK AND
TO COMPLY WITH ALL APPLICABLE CODES AND REGULATIONS.
8.THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF CIRCUITS AND OUTLETS, LOCATIONS OF SWITCHES PANEL
BOARDS, CONDUITS AND OTHER WORK. PRIOR FIELD VERIFICATION OF ALL DIMENSION IS REQUIRED. CONDUIT RUNS
AND GROUNDING ARE SHOWN DIAGRAMMATICALLY ONLY. FIELD VERIFY ACTUAL ROUTING OF CONDUITS.
9.ANY PENETRATIONS MADE THROUGH A FIRE RATED ASSEMBLY SHALL BE PROPERLY SEALED TO MAINTAIN THE FIRE
RATING OF THE ASSEMBLY PER U.L. AND NFPA.
10.THE WORK SHALL INCLUDE REVISIONS, DEMOLITION, MODIFICATIONS AND REWORK OF THE EXISTING FACILITY AND
SYSTEMS AS REQUIRED FOR INSTALLATION OF NEW WORK, AND FOR CONNECTIONS BETWEEN EXISTING WORK AND
NEW WORK WHERE REQUIRED. THE WORK SHALL ALSO INCLUDE THE COMPLETION OF ELECTRICAL POWER AND
CONTROL CIRCUITS, FOR DEVICES AND EQUIPMENT THAT ARE TO REMAIN IN SERVICE, IF THE CIRCUITS ARE BROKEN BY
DEMOLITION WORK, OR BY THE REMOVAL OR CUTTING OF EXISTING BUILDING CONSTRUCTION, EXISTING DEVICES OR
EQUIPMENT. EXISTING CONDUIT WIRING SHALL BE REROUTED AND CONNECTED WHERE NECESSARY.
11.EACH BIDDER SHALL INSPECT THE SITE AS REQUIRED FOR KNOWLEDGE OF EXISTING CONDITIONS PRIOR TO BIDDING
AND FAILURE TO OBTAIN SUCH KNOWLEDGE SHALL NOT RELIEVE THE SUCCESSFUL BIDDER OF THE RESPONSIBILITY TO
MEET EXISTING CONDITIONS IN PERFORMING THE WORK UNDER THIS CONTRACT.
12.WHERE NEW WORK CANNOT BE INSTALLED WITHOUT CHANGES IN EXISTING FACILITY OR SYSTEMS OR WHERE IT IS
INDICATED ON DRAWINGS TO REWORK AN EXISTING INSTALLATION, THIS CONTRACT SHALL INCLUDE ALTERATIONS TO
EXISTING WORK AS REQUIRED TO INSTALL NEW WORK. ADDITIONS TO THE CONTRACT COST WILL NOT BE ALLOWED
BECAUSE OF THIS CONTRACTORS FAILURE TO INSPECT EXISTING CONDITIONS AT THE SITE OF THE WORK.
13.PROVIDE HACR RATED CIRCUIT BREAKERS FOR ALL HVAC EQUIPMENT.
14.CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES TO MAINTAIN WORKING CLEARANCES AS REQUIRED PER
NEC. AND FLORIDA BUILDING CODE.
CUTTING AND PATCHING
1.THE RESPONSIBILITY FOR ANY CUTTING OF CONSTRUCTION WHICH IS REQUIRED FOR THE INSTALLATION OF
ELECTRICAL WORK, SHALL BE BY THE CONTRACTOR. THE CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES
AND THE OWNER BEFORE ANY CUTTING AND OBTAIN APPROVAL FROM THE ARCHITECT/ENGINEER PRIOR TO ANY
CUTTING. ALL PATCHING, PAINTING AND FINISH SHALL BE BY THE CONTRACTOR.
2.CUTTING SHALL BE DONE WITH EXTREME CARE AND IN SUCH A MANNER THAT THE STRENGTH OF THE STRUCTURE WILL
NOT BE ENDANGERED. WHEREVER POSSIBLE, OPENINGS IN CONCRETE OR MASONRY CONSTRUCTION SHALL BE BY
CONCRETE SAW OR ROTARY CORE DRILL. OPENINGS IN ANY CONSTRUCTION SHALL BE CUT THE MINIMUM SIZE
REQUIRED FOR THE INSTALLATION OF THE WORK. ADEQUATE PROTECTION SHALL BE PROVIDED TO PREVENT DAMAGE
TO ADJACENT AREAS AND TO PREVENT DUST FROM SPREADING TO ADJACENT AREAS.
3.WHERE OPENINGS OR HOLES ARE CUT IN CONSTRUCTION AND THE CUTTING BREAKS ELECTRICAL CIRCUITRY OR
CONTROL CIRCUITRY CONDUIT AND WIRING, THEN IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REROUTE
THE CIRCUITRY CONDUIT AND REWIRING AND TO COMPLETE THE CIRCUITRY AS REQUIRED AND AS APPROVED BY THE
ARCHITECT/ENGINEER. TEMPORARY COMPLETION SHALL BE PROVIDED WHERE NECESSARY BEFORE THE PERMANENT
REROUTING AND COMPLETION WORK IS FINISHED.
4.BEFORE ANY CUTTING, PATCHING, OR FINISHING WORK IS STARTED, DUST AND MOISTURE PROTECTION SHALL FIRST BE
INSTALLED AS REQUIRED AND AS SPECIFIED IN THESE SPECIFICATIONS.
5.OPENINGS CUT IN FLOOR SHALL BE CUT BY CORE DRILLING WHERE POSSIBLE. AFTER WORK IS INSTALLED THROUGH
ANY OPENING IN FLOOR, THE OPENING AROUND THE WORK SHALL BE PATCHED AND SEALED WATERTIGHT WITH EPOXY
OR SILICONE BASED, NON-CRACKING ELASTOMERIC SEALANT.
PAINTING
1.CONTRACTOR SHALL BE RESPONSIBLE FOR REPAINTING AREAS OF CONSTRUCTION THAT ARE SCRATCHED, MARRED, OR
DAMAGED BY THE NEW CONSTRUCTION. CONTRACTOR SHALL MATCH THE COLOR, TYPE AND THICKNESS OF PAINT AS
PREVIOUS.
ACCEPTANCE TESTING
1.UPON COMPLETION OF WORK, THE ENTIRE WIRING SYSTEM SHALL BE TESTED, AND SHALL BE SHOWN TO BE IN PROPER
WORKING CONDITION IN ACCORDANCE WITH INTENT OF SPECIFICATIONS AND DRAWINGS. IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO HAVE ALL SYSTEMS READY FOR OPERATION AND TO HAVE AN ELECTRICIAN
AVAILABLE TO OPERATE SAME IN ACCORDANCE WITH AND UNDER THE SUPERVISION OF THE INSPECTION
REPRESENTATIVE OF THE ARCHITECT/ENGINEER. THE CONTRACTOR SHALL BE AVAILABLE TO ASSIST IN REMOVAL OF
PANEL FRONTS, ETC., TO PERMIT INSPECTION AS REQUIRED.
AS-BUILT DRAWINGS
1.THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO DATE A COMPLETE RECORD SET OF CONSTRUCTION "AS-BUILTS"
BLUE LINE PRINTS WHICH SHALL BE CORRECTED DAILY, AND SHALL SHOW EVERY CHANGE FROM THE ORIGINAL
CONTRACT DRAWINGS, INCLUDING ADDENDA AND CHANGE ORDERS IN ACCORDANCE WITH GENERAL REQUIREMENTS
AND SPECIAL CONDITIONS. THIS SET OF PRINTS SHALL BE KEPT ON THE JOB SITE, AND SHALL BE USED ONLY AS A
RECORD SET. THIS SHALL NOT BE CONSTRUED AS AUTHORIZATION FOR THE CONTRACTORS TO MAKE CHANGES IN THE
LAYOUT WITHOUT DEFINITE INSTRUCTION IN EACH CASE.
PROTECTION
1.THE CONTRACTOR SHALL KEEP THE CONSTRUCTION SITE CLEAN OF ALL WASTE MATERIALS AND RUBBISH CAUSED BY
HIS WORK OR EMPLOYEES. UPON COMPLETION OF THE WORK AND AT TIMES DURING PROGRESS OF THE WORK WHEN
REQUESTED BY THE ARCHITECT/ENGINEER, THE CONTRACTOR SHALL REMOVE ALL SURPLUS MATERIALS, RUBBISH,
AND DEBRIS RESULTING FROM THE OPERATION, AND SHALL LEAVE THE ENTIRE BUILDING AND INVOLVED PORTIONS OF
THE SITE, INSOFAR AS THE WORK OF THE CONTRACT IS CONCERNED, IN A NEAT, CLEAN, AND ACCEPTABLE CONDITION
AS APPROVED BY THE ARCHITECT/ENGINEER. EQUIPMENT, LIGHTING FIXTURES, MATERIALS AND ACCESSORIES SHALL
BE THOROUGHLY CLEANED OF CEMENT, PLASTER, AND OTHER MATERIALS.
2.THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION, WHEREVER WORK IS TO BE PERFORMED IN
FINISHED/OCCUPIED SPACES, TO PREVENT DAMAGE TO ADJACENT AREAS, EQUIPMENT, OR FURNISHINGS; TO PREVENT
ACCIDENTAL INJURY TO BUILDING OCCUPANTS AND THE PUBLIC; TO PREVENT THE SPREADING OF DUST, DIRT, DEBRIS,
AND MOISTURE FROM THE AREA WHERE WORK IS BEING PERFORMED; AND TO PREVENT DUST, DIRT, DEBRIS, AND
MOISTURE FROM GETTING ON OR IN THE BUILDING OCCUPANTS FURNISHINGS OR EQUIPMENT.
3.THE CONTRACTOR SHALL REPAIR, AT NO COST TO THE OWNER, ANY DAMAGE DONE BY HIMSELF OR HIS EMPLOYEES.
HE SHALL ALSO BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED TO PROPERLY INSTALL HIS WORK. THIS
SHALL ALSO INCLUDE THE PATCHING OF EXISTING ROADWAYS (PAVED OR IMPROVED), PARKING AREAS, SIDEWALKS,
CURBS, GUTTERS, ETC., CUT TO INSTALL WORK PROVIDED BY THE CONTRACTOR. PATCH WORK SHALL COMPLY WITH
THE APPLICABLE SECTIONS OF THESE SPECIFICATIONS AND SHALL MATCH THE EXISTING FINISHES.
#
PNL P EQUIPMENT TAG
WIRELESS ACCESS POINT DESIGN BY OTHERS. CONTRACTOR SHALL COORDINATE
EXTERIOR: HUNTER JETTY OUTDOOR 52" FAN 100W; EQUALS ARE ACCEPTABLE)
POINT OF DISCONNECT
POINT OF CONNECTION
ITEM
COPY FOR
OWNER PRODUCT DATA SHOP
DRAWINGS
TEST
REPORTS
COORDINATION
DRAWINGS
WIRING
DIAGRAMS
O & M
MANUAL
1
SUBMITTAL TYPE:
1.FOR REVIEW
2.FOR RECORD
3.COLOR
SELECTION
4.SAMPLE
REMARKS:
1.FOR ALL MATERIALS FOR CONSTRUCTION, INSTALLATION REQUIREMENTS AND TESTING
REQUIREMENTS, REFER TO CONTRACT SPECIFICATIONS.
2.BEFORE PURCHASE OR FABRICATION OF EQUIPMENT AND WITHIN 30 DAYS OF AWARD OF
GENERAL CONTRACT, CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER FOR
APPROVAL, PDF COPIES OF SHOP DRAWINGS FOR ALL EQUIPMENT, LIGHTING, DEVICES, AND
MATERIALS. PARTIAL OR INCOMPLETE SUBMITTALS WILL NOT BE ACCEPTED. ANY MATERIAL
USED WITHOUT APPROVAL WILL BE REJECTED. SUBMIT SHOP DRAWINGS TO MECHANICAL AND
PLUMBING CONTRACTOR FOR APPROVAL AND COORDINATION.
3.AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING
OWNER, WITHIN 90 DAYS OF THE DAY OF RECEIVING THE CERTIFICATE OF OCCUPANCY, PER 8TH
EDITION OF THE FLORIDA BUILDING CODE - ENERGY CONSERVATION C408.3.2.2.
INCLUDE AT A MINIMUM THE FOLLOWING:
a)SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF
EQUIPMENT REQUIRING MAINTENANCE.
b)OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT
REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY
IDENTIFIED.
c)NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
5.ELECTRICAL GEAR INCLUDES ALL SWITCHBOARDS, PANELBOARDS, TRANSFORMERS, SURGE
PROTECTION DEVICES, MOTOR CONTROLLERS, DISCONNECTS, ETC.
6.ALL SUBMITTALS SHALL BE EMAILED TO INFO@DDC-ENGINEERS.COM .
7.CONTRACTOR SHALL SUBMIT ALL ITEMS UNDER ONE SUBMITTAL THAT REFERENCES DDC
PROJECT NUMBER. NO PARTIAL SUBMITTALS WILL BE ACCEPTED.
REVIEW
ALL WORK SHALL BE IN COMPLIANCE WITH THE FOLLOWING CODES, BUT NOT LIMITED TO:
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - BUILDING (FBCB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - EXISTING BUILDING (FBCEB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ACCESSIBILITY (FBCA)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ENERGY CONSERVATION (FBCEC)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - MECHANICAL (FBCM)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - PLUMBING (FBCP)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - FUEL GAS (FBCFG)
8TH EDITION OF THE 2023 FLORIDA FIRE PREVENTION CODE (FFPC)
NFPA 70 - 2020 NATIONAL ELECTRICAL CODE (NEC)
CODE COMPLIANCE REQUIREMENTS
2 3 4 1 2 1 2 1 2 1 2 1 2
ELECTRICAL GEAR
GROUNDING DEVICES
CONDUIT/FITTINGS
FEEDERS
WIRING DEVICES
LIGHTING
LIGHTING CONTROLS
GENERAL NOTES
2
A
A
A.8
A.8 B.8
A.8
3
4
5
6
MGMT.
OFFICE #1
107
MGMT.
OFFICE #2
108
CONF. RM.
109
RECEPT.
AREA
110
TRAINING #1
112
CORR.
111
TRAINING #2
113
TRAINING #3
114
TRAINING #4
115
FOYER
117CORR.
118
UTIL.
RM.
119 R.R.
120
R.R.
121
PILOT
BRIEFING RM.
123
CORR.
122
RECEPT.
OFFICE
116
DA-42
DA-44
DA-42
DA-42
DA-42
DA-40
DA-40
DA-40
DA-40
DA-40
DA-38
DA-38
DA-38
DA-38
DA-36
DA-36
DA-27
DA-27
DA-27
DA-27
DA-25
DA-25
DA-25
DA-25
DA-31 DA-33 DA-35 DA-37
DA-29
DA-29
DA-29 72"AFF
DA-29
DA-46
DA-46
60"AFF
DA-46
DA-46
DA-46
DA-46
DA-46
DA-44
DA-46
AC-2N
AC-1N
DA-23 DA-43:45
DA-39:41
EX. PNL DA
DA-36
DA-46
DA-44
DB-39
WP
DA-51:53
CU-2N
DA-43:49
WP
DB-23
CU-1N
DA-38
11
D
D C B
A
A
10
9
C.2A.9
SIMULATOR
AREA
100
OFFICE
#1
101
OFFICE
#2
102
BREAKROOM
103
UTILITY
ROOM
104
R.R.
105
R.R.
106
DB-41
DB-41
DB-43
DB-41
DB-41
DB-36 DB-36
DB-38
DB-34
DB-34
DB-34
DB-32
DB-34
DB-32DB-32DB-32DB-45
DB-45
DB-43
DB-43
DB-43
DB-45DB-45
DA-39
DA-47:49
DB-39
WP
DA-51:53
EX. PNL DB
EX AC-1S
EX CU-1S
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
E-2
EED
EL
E
C
T
R
I
C
A
L
P
O
W
E
R
P
L
A
N
JMF
DAD
NORTH BAY 3/16" = 1'-0"
ELECTRICAL POWER PLAN
SOUTH BAY 3/16" = 1'-0"
ELECTRICAL POWER PLAN
2
A
A
A.8
A.8 B.8
A.8
3
4
5
6
MGMT.
OFFICE #1
107
MGMT.
OFFICE #2
108
CONF. RM.
109
RECEPT.
AREA
110
TRAINING #1
112
CORR.
111
TRAINING #2
113
TRAINING #3
114
TRAINING #4
115
FOYER
117
CORR.
118
UTIL.
RM.
119
R.R.
120 R.R.
121
PILOT
BRIEFING RM.
123
CORR.
122
RECEPT.
OFFICE
116
DA-15
A
NL DA-34
A
A DA-15
A a
a
DA-15
A a
DA-15
A a
DA-34
A
DA-34
A
DA-34
A
DA-15
A
NL
DA-34
A
A
DA-34
a A
DA-34
a
A
DA-34
a A
DA-34
a
C
b
DA-34
C
b
DA-34
a
DA-34
A
DA-15
b A
DA-15
b A
DA-15
b
A
DA-15
a
A
DA-15
bA
DA-15
NL
A
DA-15
b
A
DA-15
b A
DA-15
b A
DA-15
b
A
DA-15
bA
DA-15
bA
DA-15
b
A
DA-15
a
A
DA-15
a
b
a
A
DA-15
c
A
DA-15
c
A
DA-15
c
A
DA-15
aA
DA-15
NL
A
DA-15
A
DA-15
a
A
DA-15
aA
DA-15
a
EF. EX EF. EX EF. EX
a
A
DA-34
A
DA-34
A
DA-34
A
DA-34
A
DA-34
A
DA-34
A
DA-34
A
DA-15
11
D
D C B
A
A
10
9
C.2A.9
SIMULATOR
AREA
100
OFFICE
#1
101
OFFICE
#2
102
BREAKROOM
103
UTILITY
ROOM
104
R.R.
105
R.R.
106
A
DB-9
EF. EX
EF. EX
A
DB-9
1TYP.
A
DB-9
A
DB-9
A
DB-9
A
DB-9
NL
A
DB-9
B
DB-9
EF. EX
B
DB-9
NL
B
DB-9
B
DB-9
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
E-3
EED
EL
E
C
T
R
I
C
A
L
L
I
G
H
T
I
N
G
P
L
A
N
JMF
DAD
NORTH BAY 3/16" = 1'-0"
ELECTRICAL LIGHTING PLAN
INTERIOR LIGHTING POWER DENSITY
ENERGY USE VS. ALLOWANCE SUMMARY - FBC C405.3.2(1)/C405.3.2(2)
OFFICE
CORRIDOR
TOTAL
ALLOWANCE LUMINARIES
AREA
(Sq.Ft.)
ALLOWED
(W/Sq.Ft.)
ALLOWED
WATTS #TYPE WATT DESIGNED
WATTS
DESIGNED
(W/Sq.Ft.)
483
517.6
0.74 320.4 9 A 35.8 322.2
0.41 212.2
4 A 35.8
1791.1
AREA
CONFERENCE ROOM 284 0.97 275.5 2 C 20
TRAINING ROOM 471 0.71 334.4 6 A 35.8
143.2
40
214.8
1722
RECEPTION 814 0.84 683.8
SOUTH BAY 3/16" = 1'-0"
ELECTRICAL LIGHTING PLAN
1.PROVIDE ALL EMERGENCY DEVICES WITH
BATTERY BACKUP, MINIMUM 90 MINUTES.
2.EXIT SIGNS SHALL BE PROVIDE WITH ARROWS
AS DIRECTED ON PLANS.
3.CONTRACTOR SHALL COORDINATE ALL
RECESSED LIGHTING WITH CEILING TYPES
AND PROVIDE DRYWALL KITS AS REQUIRED.
4.CONTRACTOR SHALL COORDINATE ALL
EXTERIOR FIXTURE FINISHES WITH
ARCHITECT/OWNER PRIOR TO PURCHASING.
5.ALL LIGHTING SHALL BE CONTROLLED BY
SENSORSWITCH OR EQUAL.
MARK DESCRIPTION QTY.
LAMPS
WATTS TYPE DIFFUSER MOUNTING VOLTAGE MANUFACTURER
NOTES:
LIGHTING SCHEDULE
B 1x4 RECESSED FLAT PANEL LED FIXTURE 33.7 LED ACRYLIC RECESSED UNV LITHONIA CPX 1X4 AL07 SWW7 M4
A 2x2 RECESSED FLAT PANEL LED FIXTURE 35.8 LED ACRYLIC RECESSED UNV LITHONIA CPX 2X2 AL07 SWW7 M4
C 4" RECESSED DOWNLIGHT 20 LED 3500K RECESSED UNV WILLIAMS 4DR-TL-L20/835-DIM-UNV-OW-OF-CS-N-F1
12 A 35.8 429.6
16 A 35.8 572.8
INTERIOR LIGHTING POWER DENSITY
ENERGY USE VS. ALLOWANCE SUMMARY - FBC C405.3.2(1)/C405.3.2(2)
OFFICE
CORRIDOR
TOTAL
ALLOWANCE LUMINARIES
AREA
(Sq.Ft.)
ALLOWED
(W/Sq.Ft.)
ALLOWED
WATTS #TYPE WATT DESIGNED
WATTS
DESIGNED
(W/Sq.Ft.)
182
73
0.74 134.7 4 A 35.8 143.2
0.41 29.9
1002.3
AREA
TRAINING ROOM 1120 0.71 795.2 4 B 33.7
BREAK ROOM 72 0.59 42.5 1 A 35.8
134.8
35.8
385.4
2 A 35.8 71.6
REVIEW SET
David A. DaSilva
54739
CONSULTANTS:
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
DE
S
C
R
I
P
T
I
O
N
NO
.
DA
T
E
REVISIONS
Copyright 2024, DDC Engineering, Inc.
24085
MAY 14, 2024
SE
B
A
S
T
I
A
N
H
A
N
G
A
R
O
F
F
I
C
E
S
B
U
I
L
D
O
U
T
SO
U
T
H
&
N
O
R
T
H
B
A
Y
S
O
F
H
A
N
G
A
R
D
SE
B
A
S
T
I
A
N
M
U
N
I
C
I
P
A
L
A
I
R
P
O
R
T
SE
B
A
S
T
I
A
N
,
F
L
O
R
I
D
A
3
2
9
5
8
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.:
This item has been electronically signed and sealed by David A.
DaSilva, PE #54739. On May 14, 2024, using a Digital Signature.
Printed copies of this document are not considered signed and
sealed, and all SHA-1 authentication code and signature must be
verified on any electronic copies.
E-4
EED
EL
E
C
T
R
I
C
A
L
P
A
N
E
L
S
C
H
E
D
U
L
E
S
JMF
DAD
TOTAL
DESIGN LOADDFLFCONN. LOADEQUIPMENT SERVED
1
CKT. BKR.KVA POLE/TR Ø N GND C
BRANCH CKTNOTESCKT
NO.Ø
AMPS
CNO.
CKT BRANCH CKT
GNDNØPOLE/TRKVACKT. BKR.
A
B
C
3
5
7
15
13
11
9
C
B
A
C
B
A
C
B
A
C
B
A
C
B
A
C
B
A
25
27
29
31
23
21
19
17
41
39
37
35
33
2
34
36
38
40
42
18
20
22
24
32
30
28
26
10
12
14
16
8
6
4
EQUIP
NO.EQUIPMENT SERVED EQUIP
NO.EQUIPMENT SERVED NOTES
C
B
A
47
45
43 44
46
48
C
B
A
53
51
49 50
52
54
TYPE
PANEL TYPE:
PANEL LOCATION:
FED FROM SOURCE:
TYPE
BUS AMP RATING:
MAIN TYPE:
VOLTAGE:
PHASE:
WIRE:
LUG LOCATION:
MOUNTING:
AIC RATING:
MAIN AMP RATING:
NOTES:
TC -WIRE THROUGH CONTACTOR
HACR -HACR TYPE BREAKER
LO -LOCKOUT BREAKER
GFCI -GND FAULT CURRENT
INTERRUPT CIRCUIT BREAKER
IG -ISOLATED GROUND
WIF -WALK IN FREEZER
WIC -WALK IN COOLER
CONNECTION TYPE
R - RECEPTACLE
L - LIGHTING
H - HVAC/EWH
K - KITCHEN EQUIPMENT
M - MISC.
PANEL:
120/208
3
4
DA (EXISTING)
EXISTING
UTILITY #115
MAIN DISCONNECT #2
225 A
200 A
MLO
EXISTING
EXISITNG
EXISITNG
REMARKS:
-PROVIDE NEW TYPE WRITTEN DIRECTORY.
-CONTRACTOR SHALL CONFIRM HVAC CIRCUIT BREAKER
REQUIREMENTS BEFORE PURCHASING.
-HEAT/COOLING LOADS ARE MUTUALLY EXCLUSIVE.
-PROVIDE FAULT CURRENT MARKER PER NEC 110.24
-PROVIDE ARC-FLASH DECALS PER NEC 110.16.
-AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH OR
EXCEED AIC RATING OF EXISTING CIRCUIT BREAKERS.
RECEPTACLES (FIRST 10 KVA)10.0 1.00 10.0
RECEPTACLES (REMAINING KVA)11.13 0.50 5.57
LIGHTING 8.27 1.25 10.33
HVAC/EWH 21.6 1.00 21.6
KITCHEN EQUIPMENT 0 1.00 0
MISC.0 1.00 0
47.5 KVA
132
R AC-1,2N / CU-1N, 2N SERVICE REC..540 1/20 12 12 12 1/2"
R PILOT BRIEFING .900 1/20 12 12 12 1/2"
R RECEPTION .900 1/20 12 12 12 1/2"
R RECEPTION .900 1/20 12 12 12 1/2"
R RECEPTION COUNTER .720 1/20 12 12 12 1/2"
RECEPTION COUNTER 1.00 1/20 12 12 12 1/2"
RECEPTION COUNTER 1.00 1/20 12 12 12 1/2"
RECEPTION COUNTER 1.00 1/20 12 12 12 1/2"
H AC-1N HACR 10.0 2/60 6 -10 1"
6
H AC-2N HACR 10.0 2/60 6 -10 1"
6
H CU-1N HACR 5.00 2/50 8 -10 1"
8
H CU-1N HACR 5.00 2/50 8 -10 1"
8
L GENERAL/ EMERGENCY .650 1/20 12 12 12 1/2"
R RECEPTION OFFICE .540 1/20 12 12 12 1/2"
R TRAINING #3 & #4 .900 1/20 12 12 12 1/2"
R TRAINING #1 & #2 .720 1/20 12 12 12 1/2"
R MGNT. OFFICE #1 .900 1/20 12 12 12 1/2"
R MGNT. OFFICE #2 .900 1/20 12 12 12 1/2"
R CONF. RM 1.44 1/20 12 12 12 1/2"
TOTAL
DESIGN LOADDFLFCONN. LOADEQUIPMENT SERVED
1
CKT. BKR.KVA POLE/TR Ø N GND C
BRANCH CKTNOTESCKT
NO.Ø
AMPS
CNO.
CKT BRANCH CKT
GNDNØPOLE/TRKVACKT. BKR.
A
B
C
3
5
7
15
13
11
9
C
B
A
C
B
A
C
B
A
C
B
A
C
B
A
C
B
A
25
27
29
31
23
21
19
17
41
39
37
35
33
2
34
36
38
40
42
18
20
22
24
32
30
28
26
10
12
14
16
8
6
4
EQUIP
NO.EQUIPMENT SERVED EQUIP
NO.EQUIPMENT SERVED NOTES
C
B
A
47
45
43 44
46
48
C
B
A
53
51
49 50
52
54
TYPE
PANEL TYPE:
PANEL LOCATION:
FED FROM SOURCE:
TYPE
BUS AMP RATING:
MAIN TYPE:
VOLTAGE:
PHASE:
WIRE:
LUG LOCATION:
MOUNTING:
AIC RATING:
MAIN AMP RATING:
NOTES:
TC -WIRE THROUGH CONTACTOR
HACR -HACR TYPE BREAKER
LO -LOCKOUT BREAKER
GFCI -GND FAULT CURRENT
INTERRUPT CIRCUIT BREAKER
IG -ISOLATED GROUND
WIF -WALK IN FREEZER
WIC -WALK IN COOLER
CONNECTION TYPE
R - RECEPTACLE
L - LIGHTING
H - HVAC/EWH
K - KITCHEN EQUIPMENT
M - MISC.
PANEL:
120/208
3
4
DB (EXISTING)
EXISTING
UTILITY ROOM 104
MAIN DISC. #1
225 A
200 A
MLO
EXISTING
EXISTING
EXISTING
RECEPTACLES (FIRST 10 KVA)10.0 1.00 10.0
RECEPTACLES (REMAINING KVA)10.14 0.50 5.07
LIGHTING 4.76 1.25 5.95
HVAC/EWH 13.2 1.00 13.2
KITCHEN EQUIPMENT 0 1.00 0
MISC.0 1.00 0
34.2 KVA
95
REMARKS:
-PROVIDE NEW TYPE WRITTEN DIRECTORY.
-CONTRACTOR SHALL CONFIRM HVAC CIRCUIT BREAKER
REQUIREMENTS BEFORE PURCHASING.
-HEAT/COOLING LOADS ARE MUTUALLY EXCLUSIVE.
-PROVIDE FAULT CURRENT MARKER PER NEC 110.24
-PROVIDE ARC-FLASH DECALS PER NEC 110.16.
-AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH OR
EXCEED AIC RATING OF EXISTING CIRCUIT BREAKERS.
R AC-1S & CU-1S DERVICE REC..360 1/20 12 12 12 1/2"
R OFFICE #1 .720 1/20 12 12 12 1/2"
R OFFICE #2 .720 1/20 12 12 12 1/2"
R SIMULATOR AREA .720 1/20 12 12 12 1/2"
H AC-1S HACR 10.0 2/60 6 -10 1"
6
H CU-1S HACR 5.00 2/50 8 -10 1"
8
R SIMULATOR AREA .720 1/20 12 12 12 1/2"
R SIMULATOR AREA .720 1/20 12 12 12 1/2"
R BREAK ROOM 1.00 1/20 12 12 12 1/2"
R BREAK ROOM 1.00 1/20 12 12 12 1/2"
(E) - EXISTING
N.T.S.
EQUIPMENT NAMEPLATE
E-D101
AHU-X
480V, 3Ø
FED FROM "NDH1-4"
AHU-X
480V, 3Ø
FED FROM "NDH1-4"
TYPICAL EQUIPMENT
116" THICK WHITE PLASTIC
WITH COLORED FACE PER
SPECIFICATIONS.
1 2" HIGH LETTERING FOR
PANELBOARD NAME.
1 4" HIGH LETTERING FOR
REMAINING TEXT.
ADHESIVE BACKING WHEN
INSTALLED IN CONDITIONED
SPACES.
EQUIPMENT NAME.
EQUIPMENT VOLTAGE
AND PHASE.
EQUIPMENT SOURCE
(PANEL & CIRCUIT)
FASTEN WITH BRASS
SCREWS WHEN LOCATED
IN NON-CONDITIONED OR
EXTERIOR SPACES
1"
M
I
N
.
2.5" MIN.
E2 N.T.S.
NAMEPLATE
E-D102
PANEL "XXXX"
120/208V, 3Ø, 4W
FED FROM PANEL "XXXX"
VIA T-XXX
PANEL "XXX"
277/408V, 3Ø, 4W
FED FROM PANEL "XXXX"
TYPICAL 120/208V PANELBOARD
TYPICAL 120/208V PANELBOARD
1 2" HIGH LETTERING
FOR PANELBOARD
NAME
1 4" HIGH LETTERING
FOR REMAINING TEXT
116" THICK WHITE PLASTIC
WITH COLORED FACE PER
SPECIFICATIONS
PANELBOARD NAME
PANELBOARD VOLTAGE
PANELBOARD SOURCE
1"
M
I
N
.
2.5" MIN.
PANELBOARDE3
54
"
N.T.S.
MOUNTING HEIGHT DETAIL
E-D100
42" A.F.F. W/ 36" COUNTER,
39" A.F.F. W/ 30" COUNTER,
48" A.F.F. WITHOUT COUNTER
OR AS NOTED ON PLANS.
EXIT
F
78
"
M
A
X
.
TO
T
O
P
D
E
V
I
C
E
36
"
A
F
F
PANELBOARD
WALL MOUNTED LIGHT FIXTURES
AS NOTED ON PLANS
6"
A
F
C
DUPLEX RECEPTACLE
1
1
℄90
"
CENTER BETWEEN DOOR AND CEILING
(COORDINATE WITH ARCHITECT)
℄
CENTER OVER DOOR
(WHERE APPLICABLE)
℄
48
"
FINISHED FLOOR
℄
SWITCH
FA PULL STATION
FIRE HORN (OR CHIME) & LIGHT
80" AFF FROM BOTTOM OF DEVICE.
TELEVISION
OUTLET
CLOCK
OUTLET
80
"
℄
VOLUME CONTROL
REMOTE TEST
TELEPHONE
OUTLET
COMPUTER OUTLET
℄
18
"
A
F
F
℄
SPECIAL POWER OUTLET
TELEPHONE OUTLET
DUPLEX RECEPTACLE
E1
N.T.S.
COVERPLATE
E-D102
DEVICE
PANEL-CIRCUIT
PANEL-CIRCUIT
1 2" HIGH P-TOUCH LABEL,
BLACK TEXT ON CLEAR
BACKROUND COLOR
RECEPTACLE
COVER PLATE
SWITCH
COVER PLATE
1 4" HIGH LETTERING FOR
PANEL NAME AND
CIRCUIT NUMBER
1 4" HIGH LETTERING FOR
PANEL NAME AND
CIRCUIT NUMBER
12" HIGH P-TOUCH LABEL,
BLACK TEXT ON CLEAR
BACKROUND COLOR
E4