SEBASTIAN CONSTRUCTION BOARD - APRIL 23, 1985
MEETING WAS CALLED TO ORDER BY CHAiRMAN HARRIS AT 7:30 P.M.
PRESENT: MR. MOLER, MR. TRIPP, MR. PALMER, CHAIRMAN HARRIS, CITY
ATTORNEY PALMER.
MR. CHUCK NEUBERGER, CITY ELECTRICAL AND MECHANICAL INSPECTOR.
ABSENT: VICE CHAIRMAN CAREY, MR. LEWIS, EXCUSED, MR. RIZIO, UNEXCUSED.
SHORTLY AFTER THE MEETING WAS CALLED TO ORDER CHAIRMAN HARRIS DISMISSED
ATTORNEY PALMER STATING THE MEETING WOULD BE STRICTLY DISCUSSION AND
THAT A ROUGH DRAFT WOULD BE PREPARED AND GIVEN TO HIM TO THEN BE BROUGHT
BACK TO THE. BOARD TO ACT ON.
A LENGTHY DISCUSSION FOLLOWED PERTAINING TO ORDINANCE 0-83-14, PAGES
8 THROUGH 12 AT WHICH TIME CHANGES WERE MADE, AS PER ATTACHED.
MR. NEUBERGER BROUGHT THREE BROBLEMS TO THE BOARDS ATTENTION FOR
DISCUSSION. 1 ) PENALTY FOR PEOPLE NOT CALLING FOR FINAL INSPECTIONS~
2) EXPIRED PERMITS; 3) COMPLAINTS - JOB SITES AND TRASH.
CHAIRMAN HARRIS STATED THESE WOULD BE DISCUSSED AT THE NEXT MEETING.
THE PROBLEM OF UNLICENSED SUB-CONTRACTORS WAS DISCUSSED BRIEFLY.
CHAIRMAN HARRIS STATED THAT A FORMAL COMPLAINT IN WRITING MUST BE
BROUGHT BEFORE THE BOARD. SPECIFIC DATED AND JOBS MUST BE PRODUCED.
MOTION BY MR. TRIBP, SECONDED BY MR. MOLER TO RECESS UNTIL APRIL 29,
1985.
CARRIED.
MEETING ADJOURNED AT 10:55 P.M.
SEBASTIAN CONSTRUCTION BOARD - APRIL 23, 1.9~8.5.
PROPOSED CHANGES TO CITY 'ORDINANCE NO. 0-83-14:
SEC. 7-47vl INSPECTIONS
(2) ALL RACEWAYS, WIRE AND/OR APPROVED CABLE, SHALL BE IN PLACE AND
ALL JOINTS MADE WITH AN APPROVED MECHANICAL CONNECTORS. SERVICE SWITCH,
DISTRIBUTION PANEL AND METERING CENTER MUST BE SET AND WIRED. IF DUE
TO STRUCTURAL CONDITIONS, PANELS AND~OR METERS CANNOT BE SET, WITH
SPECIAL PERMISSION FROM THE BUILDING DEPARTMENT INSPECTIONS CAN BE
GIVEN AT A LATER DATE, BUT SUCH ADAPTERS SHALL BE IN PLACE BEFORE
THE SYSTEMOTHERWISE BECOMES ENERGIZED WITH POWER. NO SUCH WIRINUCOR
INSTALLATION SHALL BE CONSIDERED READY FOR INSPECTION UNTIL COMPLETED .-
AS OUTLINED ABOVE. (CIRCUIT BREAKERS MAY BE INSTALLED FOR FINAL
INSPECTION.)
(4) IT SHALL BE UNLAWFUL TO LATHE, SEAL OR IN ANY MANNER CONCEAL
ANY ELECTRICAL WIRING OR EQUIPMENT UNTIL SAME HAS BEEN INSPECTED AND
-APPROVED.
SEC. 7-47.2 CERTIFICATE OF APPROVAL
(1) UPON THE SATISFACTORY COMPLETION OF THE SLAB, ROUGHIN-IN
INSPECTION, APPROVAL SHALL BE SO NOTED ON THE ELECTRICAL PERMIT CARD.
THIS APPROVAL SHALL GIVE THE DATE OF THE ROUGH-IN INSPECTION AND THE
rNITIALS OF THE INSPECTOR.
SEC. 7-47.4 SERVICE ENTRANCE STANDARDS
(a) ALL SERVICE MAST SHALL BE RUN IN APPROVED THREADED CONDUIT,
MINIMUM SIZE TWO INCHES WHICH MUST BE PROPERLY SECURED AND HAVE A
MINIMUM CLEARING THIRTY (30) INCHES ABOVE THE ROOF, UNLESS WRITTEN
APPROVAL IS OBTAINED FROM THE BUILDING OFFICIAL.
(c) ALL UNDER SLAB SERVICE ENTRANCE CONDUCTORS OR SUB-FEEDS SHALL
BE IN RIGID CONDUIT OR PVC #40 OR IMC.
ALL SERVICE ENTRANCE CONDUCTORS SHALL BE IN CONDUIT.
(f) ONLY THREADED METAL CONDUIT WILL BE ACCEPTED WHEN EXPOSED
TO THE WEATHER AND IT MUST BE GALVANIZED OR ITS EQUIVALENT.
(g) METER ROOMS SHALL BE PROVIDED IN ALL BUILDINGS OF MULTIPLE
OCCUPANCY {FOUR (4) OR MORE OCCUPANCIES) AND SHALL HAVE A MINIMUM
REQUIREMENT OF FOUR (4) TO EIGHT (8) METERS-FOUR (4) FEET BY SIX
(6) FEET BY SEVEN (7) FEET INSIDE DIAMETER; AND IF THE ELECTRICAL
REQUIREMENTS AND DEMAND ARE LARGER, THE METER ROOM SHALL BE INCREASED
ACCORDINGLY. THIS METER ROOM SHALL BE EQUIPPED WITH A VENTILATED DOOR,
AND APPROVED LOCK WHICH MAY BE LOCKED ONLY WITH THE APPROVAL OF THE
ELECTRICAL INSPECTOR. THE METER ROOM SHALL BE ACCESSIBLE TO ALL
OCCUPANCIES OF THE BUILDING AT ALL TIMES. THE METER ROOM SHALLBE
PROVIDED WITH ADEQUATE VENTILATION. THE PURPOSE OF THIS?BOOM SHALL
BE TO HOUSE THE MAIN SWITCH OR MAIN SWITCHES, DISCONNECTING EQUIPMENT
AND ITS CONTBOL DEVICES, TERMINAL EQUIPMENT FOR TELEPHONE SERVICE
(IN SEPARATE AREA FROM ELECTRICIAN'S AREA) AND ALL THE ELECTRIC METERS
WHICH SERVICE THE OCCUPANTS THROUGHOUT THE ENTIRE BUILDING.
PROPOSED CHANGES TO CITY ORDINANCE NO. 0-83-14
(g) continued
THE CONSTRUCTION OF THIS ROOM SHALL CONFORM TO THE SAME TYPE OF MATERIAL
AND CONSTRUCTION AS THE MAIN BUILDING, AND THERE SHALL BE NO STORAGE OF
ANY KIND, GAS METERS OR WATER HEATERS PERMITTED IN THIS ROOM.
(h) SERVICE DISCONNECT SHALL BE LOCATED AT THE NEAREST POINT OF SERVICE
ENTRY NOT TO EXCEED 5 FEET UNLESS PRECEEDED BY MAIN DISCONNECT AND SHALL
NOT BE INSTALLED IN BATHROOMS, BEDROOMS, CLOSETS OR KITCHEN CABINETS,
AND MUST BE PRECEDED BY MAIN DISCONNECT.
(i) GROUNDING OF THE MAIN SERVICE TO THE COPPER TUBING WATER SYSTEM
SHALL HAVE AN EQUAL SIZE GROUND WIRE AS THAT GOING TO THE GROUNDING
ELECTRODE. THE MINIMUN WIRE SHALL BE #4 CONTINUOUS FROM THE METER
GROUND BAR TO THE GROUNDING ELECTRODE. THEN TO A 1/2" MINIMUM COPPER
COLD WATER STUB-OUT, IF AVAILABLE. YOU MUST THEN HAVE A JUMPER BETWEEN
THE HOT AND COLD WATER PIPES ABOVE THE HOT WATER TANK BEFORE THE SHUT-OFF
VALVES, OR, FROM THE PANEL GROUND BAR TO THE HOT WATER TANK COLD WATER
LINE. THE FOLLOWING SHALL ALSO BE REQUIRED: ALL CONNECTIONS SHALL BE
VISIBLE; GROUNDING ELECTRODE CONDUCTOR MUST BE SLEEVED IF PVC IS USED
AS A SLEEVE, TEAR DROP ~T~LE CLAMPS SHALL BE USED ON GROUNDING ELECTRODES.